Product Description

 1.jpg2.jpg

 

 

  

Technical data

Type/System protection mode

BT PCM TT3+1

150 RM

(for three phase TT3+1/TN-S system)

BT PCM TT3+1

275 RM

(for three phase TT3+1/TN-S system)

BT PCM TT3+1

320 RM

(for three phase TT3+1/TN-S system)

BT PCM TT3+1

 385 RM

(for three phase TT3+1/TN-S system)

Rated voltage (max. continuous voltage) [Uc] L-N / N-PE

150V(50/60Hz) / 255V(50/60Hz)

275V(50/60Hz)/ 255V(50/60Hz)

320V(50/60Hz) / 255V(50/60Hz)

385V(50/60Hz) / 255V(50/60Hz)

Nominal discharge current (8/20μs) [In] L-N / N-PE

20kA / 40kA

20kA / 40kA

20kA / 40kA

20kA / 40kA

Max. discharge current (8/20μs) [Imax] L-N / N-PE

40kA / 65kA

40kA / 65kA

40kA / 65kA

40kA / 65kA

Voltage protection level at In [Up]

L-N / N-PE

≤ 0.9kV / ≤ 1.8kV

≤ 1.3kV / ≤ 1.8kV

≤ 1.5kV / ≤ 1.8kV

≤ 1.8kV / ≤ 1.8kV

Voltage protection level 5kA [Up]

L-N

≤ 0.7kV

≤ 1.0kV

≤ 1.2kV

≤ 1.35kV

Response time [tA]

L-N / N-PE

≤ 25ns / ≤ 100ns

≤ 25ns / ≤ 100ns

≤ 25ns / ≤ 100ns

≤ 25ns / ≤ 100ns

Max. back up fuse [F]

125A gL/gG

125A gL/gG

125A gL/gG

125A gL/gG

Operating temperature range [Tu] / Degree of protection

-40°C...+80°C / IP 20

Cross-sectional area

1.5mm2 ~ 25mm2 solid / 35mm2 flexible

Mounting on

35mm DIN rail, according to EN 60715

Enclosure material

Purple (module) & light grey (base) thermoplastic, UL94-V0

Dimension / Installation site / Port number

4 mods / indoor / 1

Class / Test standards

Class II / IEC 61643-11; GB 18802.1; YD/T 1235.1

Certification

KEMA-KEUR, CE(LVD,EMC), CB, ROHS

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Ordering information

Type

BT PCM TT3+1

150 RM

BT PCM TT3+1

275 RM

BT PCM TT3+1

320 RM

BT PCM TT3+1

385 RM

Art.-No.

810 812

810 813

810 913

810 815

Packing unit

1pc(s)

1pc(s)

1pc(s)

1pc(s)

 

Summary

BT PCM TT3+1 150/275/320/385 RM for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class II (Class C) for TT(“3+1” circuit) and TNpower supply system. Designed according to IEC 61643-11/GB 18802.1.