30+ Years SPD Factory Telebahn 275V 255V 20kA 40kA T2 1+N KEMA Surge Arrester Protective Device SPD for 1 Phase TT1+1 System
- Overview
- Inquiry
- Related Products
Technical data
Type |
BT PCM TT1+1 150 RM |
BT PCM TT1+1 275 RM |
BT PCM TT1+1 320 RM |
According to IEC 61643-11/EN 61643-11 |
Class II (class 2/C) / Type 2 |
||
System mode |
TT System (“ 1+1 ")circuit |
||
Nominal voltage [UN](50/60Hz) |
120V |
230V |
230V |
Rated voltage (max. continuous voltage) [Uc] [L-N / N-PE](50/60Hz) |
150V/255V |
275V/255V |
320V/255V |
Nominal discharge current (8/20μs) [In] [L-N / N-PE] |
20kA/40kA |
20kA/40kA |
20kA/40kA |
Max. discharge current (8/20μs) [Imax] [L-N / N-PE] |
40kA/65kA |
40kA/65kA |
40kA/65kA |
Lightning impulse current (10/350μs) [Iimp] [N-PE] |
20kA |
20kA |
20kA |
Voltage protection level at In [Up] [L-N / N-PE] |
≤ 0.9kV/ ≤ 1.5kV |
≤ 1.3kV/ ≤ 1.5kV |
≤ 1.5kV/≤ 1.5kV |
Voltage protection level at 5kA [Up] [L-N ] |
≤ 0.75kV |
≤ 1.0kV |
≤ 1.2kV |
Response time [tA] [L-N / N-PE] |
≤ 25ns/≤ 100ns |
||
Max. back up fuse [F] |
125A gL/gG |
||
Operating temperature range [Tu] / Operating state / Failure indication |
-40°C...+80°C / Green / Red |
||
Cross-sectional area |
1.5mm2 ~ 25mm2 solid / 35mm2 flexible |
||
Mounting on / Number of remote terminals |
35mm DIN rail / 1 |
||
Enclosure material |
Red (module) & light gray (base) thermoplastic, UL94-V0 |
||
Dimension / Degree of Protection |
2 mods (36mm) / IP 20 |
||
Certification |
KEMA-KEUR; CB; CE; RoHS |
||
Type of remote signaling contact |
Switching contact |
||
Switching capacity a.c. |
250V/0.5A |
||
Switching capacity d.c. |
250V/0.1A, 125V/0.2A, 75V/0.5A |
||
Cross-sectional area for remote signaling contact |
Max. 1.5mm2 solid/flexible |
||
Ordering information |
|||
Type |
BT PCM TT1+1 150 RM |
BT PCM TT1+1 275 RM |
BT PCM TT1+1 385 RM |
Art.-No. |
810 820 |
810 821 |
810822 |
Packing unit |
1pc(s) |
1pc(s) |
1pc(s) |
Hightlight Features
• Pluggable module, easy for installation and maintenance.
• Consist of varistors + GDT and thermal disconnection devices.
• High discharge capacity, quick response.
• Double thermal disconnector devices, providing more reliable protection.
• Green window will change to red when fault occurs and also provide remote alarm control at the same time.
Summary
BT PCM TT1+1 275 RM(810821) is for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class II (Class C) for Single PhaseTN/TT “1+1” circuit power supply system. Designed according to IEC 61643-11/EN 61643-11.