Technical data 

Type

BT PCM TT1+1 150 RM

BT PCM TT1+1 275 RM

BT PCM TT1+1 320 RM

According to IEC 61643-11/EN 61643-11

Class II (class 2/C) / Type 2

System mode

TT System (“ 1+1 ")circuit

Nominal voltage  [UN](50/60Hz) 

120V

230V

230V

Rated voltage (max. continuous voltage) [Uc] [L-N / N-PE](50/60Hz)

150V/255V

275V/255V

320V/255V

Nominal discharge current (8/20μs) [In] 

[L-N / N-PE]

20kA/40kA

20kA/40kA

20kA/40kA

Max. discharge current (8/20μs) [Imax] 

[L-N / N-PE]

40kA/65kA

40kA/65kA

40kA/65kA

Lightning impulse current (10/350μs) [Iimp]

[N-PE]

20kA

20kA

20kA

Voltage protection level at In [Up] 

[L-N / N-PE]

≤ 0.9kV/ ≤ 1.5kV

≤ 1.3kV/ ≤ 1.5kV

≤ 1.5kV/≤ 1.5kV

Voltage protection level at 5kA [Up] 

[L-N ]

≤ 0.75kV

≤ 1.0kV

≤ 1.2kV

Response time [tA] 

[L-N / N-PE]

≤ 25ns/≤ 100ns

Max. back up fuse [F]

125A gL/gG

Operating temperature range [Tu] / Operating state / Failure indication 

-40°C...+80°C / Green / Red 

Cross-sectional area 

1.5mm2 ~ 25mm2 solid / 35mm2 flexible

Mounting on /  Number of remote terminals

35mm DIN rail / 1

Enclosure material

Red (module) & light gray (base) thermoplastic, UL94-V0

Dimension /  Degree of Protection 

2 mods (36mm) / IP 20

Certification

KEMA-KEUR; CB; CE; RoHS

Type of remote signaling contact

Switching contact

Switching capacity a.c.

250V/0.5A

Switching capacity d.c.

250V/0.1A, 125V/0.2A, 75V/0.5A

Cross-sectional area for remote signaling contact

Max. 1.5mm2 solid/flexible

Ordering information

Type

BT PCM TT1+1 150 RM

BT PCM TT1+1 275 RM

BT PCM TT1+1 385 RM

Art.-No.

810 820

810 821

810822

Packing unit

1pc(s)

1pc(s)

1pc(s)

 

Image2.jpgDimension.jpgMounting.jpg

Hightlight Features

•  Pluggable module, easy for installation and maintenance.

•  Consist of varistors + GDT and thermal disconnection devices.

•  High discharge capacity, quick response.

•  Double thermal disconnector devices, providing more reliable protection.

•  Green window will change to red when fault occurs and also provide remote alarm control at the same time.