 16.jpg17.jpg

Technical Data

Type

BT P C 150 RM

BT P C 2P 150 RM

BT P C 3P 150 RM

BT P C 4P 150 RM

System protection mode / Nominal a.c. voltage [Un]

Single-pole

120V(50/60Hz)

Single-phase TN System

120V(50/60Hz)

 

Three-phase TN-C System

120V/240V(50/60Hz)

Three-phase TN-S/TT System

120V/240V(50/60Hz)

Rated voltage(max. continuous a.c. voltage) [ Uc ]

150V(50/60Hz)

Nominal discharge current(8/20μs[ In ] 

20kA

Nominal discharge current(8/20μs[ Imax ] 

40kA

Voltage protection level at 5kA [ Up ]  

≤ 0.55kV

Voltage protection level at In [ Up ] 

≤ 0.7kV

Response time [ tA ] 

25ns 

MOV voltage

150V/5sec

Max. Back up fuse(L)

125A gL/gG

 Operating temperature range 

[Tu] Degree of protection

-40°C...+80°C  / IP 20 

 

Cross-section area

1.5mm2 -25mm2 (solid)/ 35mm2 (flexible)

Mounting on

35mm DIN railaccording to EN 60715 

Enclosure material / Installation site / Remote Terminal 

Purple module thermoplastic, UL94-V0 /  indoor / 1

Dimension  

1 mod (18mm) 

2 mods (36mm) 

3 mods (54mm) 

4 mods  (72mm) 

Test standards

IEC 61643-11; EN 61643-11;  GB/T 18802.11;YD/T 1235.1

Certification

CE (LVD, EMC); RoHS

Type of remote signalling contact

Switching contact

Switching capacity a.c

AC: 250V/0.5A

Switching capacity d.c

DC: 250V/0.1A; 150V/0.2A; 750V/0.5A

Cross-sectional area for remote signalling contact

Max 1.5mm2 (solid/flexible)

Ordering information

Type

BT P C 150 RM

BT P C 2P 150 RM

BT P C 3P 150 RM

BT P C 4P 150 RM

Art.-No.

810 007

810 203

810 130

810 141

Packing unit

1pc(s)

1pc(s)

1pc(s)

1pc(s)

 

1 

FAQ

GET IN TOUCH