All Categories
AC SPD Class II

AC SPD Class II

Factory Wholesale 230V 75V 150V 275V 320V 385V 440V 600V MOV T2 1P 2P 3P 4P AC 20kA 40kA SPD Surge Arrester Suppressor Protector

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description

 16.jpg17.jpg

Technical Data

Type

BT P C 385 RM

BT P C 2P 385 RM

BT P C 3P 385 RM

BT P C 4P 385 RM

System protection mode  Nominal a.c. voltage [Un](50/60Hz)

Single-pole

230V

Single-phase TN System

230V

Three-phase TN-C System

230V/400V

Three-phase TN-S/TT System

230V/400V

Rated voltage(max. continuous a.c. voltage) [ Uc ](50/60Hz)

385V

Nominal discharge current(8/20μs[ In ] 

20kA

Nominal discharge current(8/20μs[ Imax ] 

40kA

Voltage protection level at 5kA [ Up ]  

≤ 1.35kV

Voltage protection level at In [ Up ] 

1.8kV

Response time [ tA ] 

25ns 

MOV voltage

385V/5sec

Max. Back up fuse(L)

125A gL/gG

 Operating temperature range 

[Tu] Degree of protection

-40°C...+80°C / IP 20

 

Cross-section area

1.5mm2 -25mm2 (solid)/ 35mm2 (flexible)

Mounting on

35mm DIN rail

Enclosure material  Installation site / Remote Terminal 

Purple module thermoplastic, UL94-V0  indoor / 1

Dimension

1 mod (18mm) 

2 mods (36mm) 

3 mods (54mm) 

4 mods  (72mm) 

Test standards

IEC 61643-11; EN 61643-11;  GB/T 18802.11;YD/T 1235.1

Certification

CE (LVD, EMC); RoHS

Type of remote signalling contact

Switching contact

Switching capacity a.c

AC: 250V/0.5A

Switching capacity d.c

DC: 250V/0.1A; 150V/0.2A; 750V/0.5A

Cross-sectional area for remote signalling contact

Max 1.5mm2 (solid/flexible)

Ordering information

Type

BT P C 385 RM

BT P C 2P 385 RM

BT P C 3P 385 RM

BT P C 4P 385 RM

Art.-No.

810 010

810 201

810 134

810 143

Packing unit

1pc(s)

1pc(s)

1pc(s)

1pc(s)

 

1 

FAQ

GET IN TOUCH