Product Description

 16.jpg17.jpg

Technical Data

Type

BT P C 385 RM

BT P C 2P 385 RM

BT P C 3P 385 RM

BT P C 4P 385 RM

System protection mode/ Nominal a.c. voltage [Un](50/60Hz)

Single-pole

230V

Single-phase TN System

230V

Three-phase TN-C System

230V/400V

Three-phase TN-S/TT System

230V/400V

Rated voltage(max. continuous a.c. voltage) [ Uc ](50/60Hz)

385V

Nominal discharge current(8/20μs[ In ] 

20kA

Nominal discharge current(8/20μs[ Imax ] 

40kA

Voltage protection level at 5kA [ Up ]  

≤ 1.35kV

Voltage protection level at In [ Up ] 

1.8kV

Response time [ tA ] 

25ns 

MOV voltage

385V/5sec

Max. Back up fuse(L)

125A gL/gG

 Operating temperature range 

[Tu] Degree of protection

-40°C...+80°C / IP 20

 

Cross-section area

1.5mm2 -25mm2 (solid)/ 35mm2 (flexible)

Mounting on

35mm DIN rail

Enclosure material / Installation site / Remote Terminal 

Purple module thermoplastic, UL94-V0  indoor / 1

Dimension

1 mod (18mm) 

2 mods (36mm) 

3 mods (54mm) 

4 mods  (72mm) 

Test standards

IEC 61643-11; EN 61643-11;  GB/T 18802.11;YD/T 1235.1

Certification

CE (LVD, EMC); RoHS

Type of remote signalling contact

Switching contact

Switching capacity a.c

AC: 250V/0.5A

Switching capacity d.c

DC: 250V/0.1A; 150V/0.2A; 750V/0.5A

Cross-sectional area for remote signalling contact

Max 1.5mm2 (solid/flexible)

Ordering information

Type

BT P C 385 RM

BT P C 2P 385 RM

BT P C 3P 385 RM

BT P C 4P 385 RM

Art.-No.

810 010

810 201

810 134

810 143

Packing unit

1pc(s)

1pc(s)

1pc(s)

1pc(s)

 