All Categories
AC SPD Class I

AC SPD Class I

Telebahn TUV CE CB RoHS 3P+NPE T1+T2 Uc150V 275V 300V 320V 385V 440V Iimp12.5kA Three Phase Power Surge Protector Device SPD

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description

 1.jpg6.jpg

 

Technical data

Type

BT P BCM12.5 275 RM/3+N

Nominal voltage ( 50/60Hz )  [UN] 

230V / 400V AC

Rated voltage (max. continuous voltage) [Uc] 

L-N / N-PE

320V / 255V AC

Lightning impulse current (10/350) [Iimp] 

L-N / N-PE

12.5kA / 37.5kA

Nominal discharge current (8/20) [In] 

L-N / N-PE

30kA / 50kA

Max. discharge current (10/350) [Imax] 

L-N / N-PE

60kA / 100kA

Total discharge current (8/20) [Itotal] 

100kA

Voltage protection level at 320V [Up] 

≤ 1.8kV

Voltage protection level at Iimp [Up] 

L-N / N-PE

≤ 1.35kV ≤ 1.5kV

Admissible  short-current [Isccr]

25kA

Response time [tA]  

L-N / N-PE

≤ 25ns ≤ 100ns

Max. back up fuse [F]

160A gL/gG

Operating temperature range [Tu]

-40°C...+80°C

Cross-sectional area

1.5mm2 ~ 25mm2 solid /35mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Light gray thermoplastic, UL94-V0

Dimension

4 mod(72mm wide)

Test standards

IEC 61643-11; EN 61643-11; GB/T18802.11

Certification

TUV; CE (LVD, EMC); CB, RoHS

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Ordering information

Type

BT P BCM12.5 275 RM/3+N

Art.-No.

801 432

Packing unit

1pc(s)

 

Summary

BT P BCM12.5 275 RM/3+N(801432) is for installation at LPZ 0A-2 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I+II (Class B+C) for  three-phase TT/TN-S (3+1 circuit) power supply system. Designed according to IEC 61643-11/EN 61643-11/GB18802.11.

1