Summary

BT PBM120 275 RM/2P is for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I (Class B) for single-phase TN power supply system. Designed according to IEC 61643-11; GB/T18802.11.

Highlight Features

  8/20μs varistors for max. discharge current up to 120kA.

  Combined lightning current arrester for single-phase TN ( 2+0 circuit) system.

  High discharge capacity, quick response. 

  Consist of varistors and thermal disconnection devices.  

  Multifunctional connection for conductors and busbar.

  Windows will change to red when fault and also provide remote alarm control at the same time.

Technical data

Type

BT PBM120 275 RM/2P

Nominal voltage  [UN] 

230V AC

Rated voltage (max. continuous voltage) [Uc] 

275V AC

Nominal discharge current (8/20) [In] 

60kA

Max. discharge current (8/20) [Imax] 

120kA

Voltage protection level at In [Up] 

2.2kV

Response time [tA] 

≤ 25ns

TOV voltage

335V/5sec

Max. back up fuse [L]

200A gL/gG

Max. back up fuse [L-L’]

125A gL/gG

Operating temperature range [Tu]

-40°C...+80°C

Cross-sectional area

35mm2 solid /50mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Light grey thermoplastic, UL94-V0

Dimension

4 mods (72mm)

Test standards

IEC 61643-11; EN 61643-11; GB/T18802.11

Certification

CE (LVD, EMC); RoHS

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Ordering information

Type

BT PBM120 275 RM/2P

Art.-No.

800 833

Packing unit

1pc(s)

Image.jpgDimension.jpgMounting.jpg

1SPD AC T1 2P 275V In60kA/Imax120kA for Single-phase TN Power Supply System Lightning Protectors manufactureSPD AC T1 2P 275V In60kA/Imax120kA for Single-phase TN Power Supply System Lightning Protectors factorySPD AC T1 2P 275V In60kA/Imax120kA for Single-phase TN Power Supply System Lightning Protectors factorySPD AC T1 2P 275V In60kA/Imax120kA for Single-phase TN Power Supply System Lightning Protectors supplierSPD AC T1 2P 275V In60kA/Imax120kA for Single-phase TN Power Supply System Lightning Protectors supplierSPD AC T1 2P 275V In60kA/Imax120kA for Single-phase TN Power Supply System Lightning Protectors supplierFAQSPD AC T1 2P 275V In60kA/Imax120kA for Single-phase TN Power Supply System Lightning Protectors details

GET IN TOUCH