Product Description

 

Class I+II Lightning current Surge Protective Devices for Three-phase TN-S Power Supply System

Image_BT P BCM 25 RM_4P.jpg6.jpgDimension_BT PBCM 25 RM_4P.jpgMounting_BT PBCM 25 RM_4P.jpg

 

 

 

Summary

For installation at LPZ 0A-1 or high, protecting low voltage equipment against lightning and surge damages. Specially designed for TN-S system. Applied in SPD Class Ⅰ (Class B) for various power supply system of lightning current surge protection. Designed according to GB 18802.1/IEC 61643-11. 

Hightlight Features

•  Combined lightning current arrester for 3-phase TN-S ( “4+0” circuit) system, Pluggable Iimp(10/350μs):25kA,In(8/20μs):50kA, Imax(8/20μs):75kA, Iimp(10/350μs)total 100kA.

•  Adopt hermetical GDT technology, high follow current extinguishing capacity.

•  Extremely low voltage protection level.

•  Double thermal disconnector devices, providing more reliable protection.

•  Green window will change to red when fault occurs, also provide remote alarm terminal  at the same time.

Application Environment

Temperature:-40°C...+80°C

Relative humidity:≤95%(25°C)

 

Technical Data

Type

BT P BCM 25 RM/4P

Nominal a.c. voltage [UN]

230V/400V~

Rated voltage (max. continuous voltage) [Uc]

255V~

Total lightning impulse current (10/350) [Iimp] 

100kA

Lightning impulse current (10/350) [Iimp] 

25kA

Nominal discharge current (8/20) [In] 

50kA

Max. discharge current (8/20) [Imax] 

75kA

Voltage protection level at In [Up] 

≤ 1.5kV

Response time [tA] 

≤ 100ns

Follow current extinguishing capability at Uc 

32A fuse will not be triggered at 2kArms 255V

Max. back up fuse (L) [F]

200A gL/gG

Max. back up fuse (L-L’) [F]

125A gL/gG

TOV voltage

335V/5sec

Min. cross-sectional area

10mm2 solid / flexible

Max. cross-sectional area

35mm2 solid / 50mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Purple (module) & light grey (base) thermoplastic, UL94-V0

Dimension

8 mods (144mm)

Test standards

IEC 61643-11; EN 61643-11; GB/T 18802.11

Certification

CE (LVD, EMC); RoHS

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Ordering information

Type

BT P BCM 25 RM/4P

Art.-No.

800 914

Packing unit

1pc(s)

 

Installation Diagram

 BT P BCM 25 RM 4P

5.jpg230V/400V/255V AC 4P TOV T1+T2 Iimp25kA/In50kA/Imax75kA for 3-phase TN-S ( 4+0 circuit) System Power SPD Lightning Protectors manufacture230V/400V/255V AC 4P TOV T1+T2 Iimp25kA/In50kA/Imax75kA for 3-phase TN-S ( 4+0 circuit) System Power SPD Lightning Protectors manufacture230V/400V/255V AC 4P TOV T1+T2 Iimp25kA/In50kA/Imax75kA for 3-phase TN-S ( 4+0 circuit) System Power SPD Lightning Protectors details230V/400V/255V AC 4P TOV T1+T2 Iimp25kA/In50kA/Imax75kA for 3-phase TN-S ( 4+0 circuit) System Power SPD Lightning Protectors manufacture230V/400V/255V AC 4P TOV T1+T2 Iimp25kA/In50kA/Imax75kA for 3-phase TN-S ( 4+0 circuit) System Power SPD Lightning Protectors manufacture230V/400V/255V AC 4P TOV T1+T2 Iimp25kA/In50kA/Imax75kA for 3-phase TN-S ( 4+0 circuit) System Power SPD Lightning Protectors manufactureFAQ230V/400V/255V AC 4P TOV T1+T2 Iimp25kA/In50kA/Imax75kA for 3-phase TN-S ( 4+0 circuit) System Power SPD Lightning Protectors details

 

 

 

 

 

 

 

 

 

 

 

 