All Categories
AC SPD Class I

AC SPD Class I

Telebahn Low Voltage Surge Protectors 385VAC T1 50kA 100kA 120kA for Three-phase TT/TN-S System Power Lightning Arresters SPD

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description

 Technical data

Type

BT PBM100 385 RM/3+N

Single-pole protection module

BT PBM100 385 RM (*3)

(L-N module)

BT PBNM 255 RM (*1)

(N-PE module)

Nominal a.c. voltage [UN] 

230V/400V AC

Total discharge current (8/20) [In total]

120kA

Rated voltage (max. continuous voltage) [Uc] 

L-N / N-PE

385V AC

255V AC

Nominal discharge current (8/20) [In] 

L-N / N-PE

50kA

100kA

Max. discharge current (8/20) [Imax] 

100kA

120kA

Lightning impulse current (10/350) [Iimp]

N-PE

/

25kA

Voltage protection level at In [Up] 

L-N / N-PE

2.0kV

2.5kV

Response time [tA] 

L-N / N-PE

25ns 

100ns 

TOV voltage 

L-N / N-PE

355V / 5sec

1200V / 200ms

Max. back up fuse

125A gL/gG

Operating temperature range [Tu]

-40°C...+80°C

Cross-sectional area

35mm2 solid /50mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Pruple (Module) / Light gray (Base) thermoplastic, UL94-V0

Dimension

8 mods (144mm)

Test standards

IEC 61643-11; EN 61643-11; GB18802.11

Certification

CE (LVD, EMC); RoHS

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Ordering information

Type

BT PBM100 385 RM/3+N

Art.-No.

800 829

Packing unit

1pc(s)

Image_BT PBM120 275 RM_3+N.jpgDimension.jpg

Mounting.jpg

Hightlight Features

  8/20us varistor,  Max.discharge current up to Imax 100kA (L-N module)/120kA (N-PE module).

  Combined lightning current arrester for three-phase TT/TN-S (3+1 circuit) system.

  Consist of varistors and thermal disconnection devices.  

  Double thermal disconnection device, provide more reliable protection.

  Multifunctional connection for conductors and busbar.

  Green windows will change to red when fault and also provide remote alarm control at the same time.

Summary

 BT PBM100 385 RM/3+N is for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I (Class B) for three-phase TT/TN-S (3+1 circuit) power supply system. Designed according to IEC 61643-11/EN 61643-11/GB18802.11.

5.jpgFAQ

 

 

 

GET IN TOUCH