All Categories
AC SPD Class I

AC SPD Class I

Telebahn Low Voltage Surge Protectors 385VAC T1 50kA 100kA 120kA for Three-phase TT/TN-S System Power Lightning Arresters SPD

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description

 Technical data

Type

BT PBM100 385 RM/3+N

Single-pole protection module

BT PBM100 385 RM (*3)

(L-N module)

BT PBNM 255 RM (*1)

(N-PE module)

Nominal a.c. voltage [UN] 

230V/400V AC

Total discharge current (8/20) [In total]

120kA

Rated voltage (max. continuous voltage) [Uc] 

L-N / N-PE

385V AC

255V AC

Nominal discharge current (8/20) [In] 

L-N / N-PE

50kA

100kA

Max. discharge current (8/20) [Imax] 

100kA

120kA

Lightning impulse current (10/350) [Iimp]

N-PE

/

25kA

Voltage protection level at In [Up] 

L-N / N-PE

≤ 2.0kV

≤ 2.5kV

Response time [tA] 

L-N / N-PE

≤ 25ns 

≤ 100ns 

TOV voltage 

L-N / N-PE

355V / 5sec

1200V / 200ms

Max. back up fuse

125A gL/gG

Operating temperature range [Tu]

-40°C...+80°C

Cross-sectional area

35mm2 solid /50mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Pruple (Module) / Light gray (Base) thermoplastic, UL94-V0

Dimension

8 mods (144mm)

Test standards

IEC 61643-11; EN 61643-11; GB18802.11

Certification

CE (LVD, EMC); RoHS

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Ordering information

Type

BT PBM100 385 RM/3+N

Art.-No.

800 829

Packing unit

1pc(s)

Image_BT PBM120 275 RM_3+N.jpgDimension.jpg

Mounting.jpg

Hightlight Features

•  8/20us varistor,  Max.discharge current up to Imax 100kA (L-N module)/120kA (N-PE module).

•  Combined lightning current arrester for three-phase TT/TN-S (“3+1” circuit) system.

•  Consist of varistors and thermal disconnection devices.  

•  Double thermal disconnection device, provide more reliable protection.

•  Multifunctional connection for conductors and busbar.

•  Green windows will change to red when fault and also provide remote alarm control at the same time.

Summary

 BT PBM100 385 RM/3+N is for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I (Class B) for three-phase TT/TN-S (“3+1” circuit) power supply system. Designed according to IEC 61643-11/EN 61643-11/GB18802.11.

5.jpgTelebahn Low Voltage Surge Protectors 385VAC T1 50kA 100kA 120kA for Three-phase TT/TN-S System Power Lightning Arresters SPD factoryTelebahn Low Voltage Surge Protectors 385VAC T1 50kA 100kA 120kA for Three-phase TT/TN-S System Power Lightning Arresters SPD supplierTelebahn Low Voltage Surge Protectors 385VAC T1 50kA 100kA 120kA for Three-phase TT/TN-S System Power Lightning Arresters SPD supplierTelebahn Low Voltage Surge Protectors 385VAC T1 50kA 100kA 120kA for Three-phase TT/TN-S System Power Lightning Arresters SPD manufactureTelebahn Low Voltage Surge Protectors 385VAC T1 50kA 100kA 120kA for Three-phase TT/TN-S System Power Lightning Arresters SPD detailsTelebahn Low Voltage Surge Protectors 385VAC T1 50kA 100kA 120kA for Three-phase TT/TN-S System Power Lightning Arresters SPD detailsFAQTelebahn Low Voltage Surge Protectors 385VAC T1 50kA 100kA 120kA for Three-phase TT/TN-S System Power Lightning Arresters SPD supplier

 

 

 

GET IN TOUCH