Technical data
Combined Type |
BT BCM 25 RM/2P |
Nominal voltage a.c. [ UN ] |
230V |
Rated voltage (max. continuous a.c. voltage) [ Uc ] |
255V |
Total lightning impulse current (10/350) [ Iimp ] |
50kA |
Lightning impulse current (10/350) [ Iimp ] |
25kA |
Nominal discharge current (8/20) [ In ] |
50kA |
Max. discharge current (8/20) [ Imax ] |
100kA |
Voltage protection level at In [ Up ] |
≤ 1.8kV |
Follow current extinguishing capability at Uc [ If ] |
32A fuse will not be triggered at 2kArms 255V |
Response time [tA] |
≤ 25ns |
TOV voltage [UT] |
355V / 5sec |
Max. back up fuse (L) [F] |
200A gL/gG |
Max. back up fuse (L-L’) [F] |
125A gL/gG |
Operating temperature range [Tu] |
-40°C...+80°C |
Min. cross-sectional area |
10mm2 solid / flexible |
Max. cross-sectional area |
35mm2 solid / 50mm2 flexible |
Mounting on |
35mm DIN rail |
Enclosure material |
Light grey thermoplastic, UL94-V0 |
Dimension |
4 mods (36mm) |
Test standards |
IEC 61643-1; EN 61643-1 |
Certification |
CE, RoHS |
Type of remote signalling contact |
Switching contact |
Switching capacity |
AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A |
Cross-sectional area for remote signalling contact |
Max. 1.5mm2 solid / flexible |
Ordering information |
|
Type |
BT BCM 25 RM/2P |
Art.-No. |
801 032 |
Packing unit |
1pc(s) |
Summary
BT BCM 25 RM/2P is for installation at LPZ 0A-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I (Class B) for TN (2+0 circuit) power supply system. Designed according to IEC 61643-11/EN 64643-11.
Hightlight Features
• 10/350μs, 8/20μs sparkgap, Single-phase lightning surge arrester.
• Lightning impulse current withstand max.25kA (10/350μs).
• Adopt hermetical GDT technology, high follow current extinguishing capacity.
• Extremely low voltage protection level.
• Double thermals for parallel or series (V-shape) connection.
• Multifunctional connection for conductors and busbars.
• Green light indicates functional mode (L-PE module).