All Categories
AC SPD Class II

AC SPD Class II

Telebahn AC DPS TVSS 3P+N 120V 150V 10kA-20kA 20kA -40kA 30kA-60kA T2 Surge Protection Device Transient Voltage Surge Suppressor

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description

 

9.jpg.png14.jpg.png

 

Technical Data

Type

BT PCM20 150 RM/3+N

BT PCM TT3+1 150 RM

BT PCM60 150 RM/3+N

According to IEC 61643-11/EN 61643-11

Class II / Type 2

Class II / Type 2

Class II / Type 2

Art.-No.

810856

810812

810816

Nominal a.c. voltage [UN]

120V/240V

120V/240V

120V/240V

Rated voltage (max. continuous a.c. voltage) [Uc](L-N/N-PE)

150V/255V

150V/255V

150V/255V

Frequency[Hz]

50/60 Hz

50/60 Hz

50/60 Hz

Nominal discharge current (8/20μs) [In](L-N/N-PE)

10kA/20kA

20kA/40kA

30kA/60kA

Max. discharge current (8/20μs) [Imax](L-N/N-PE)

20kA/40kA

40kA/65kA

60kA/65kA

Voltage protection level at In [Up](L-N/N-PE)

≤0.7kV/≤1.5kV

≤0.9kV/≤1.5kV

≤1.2kV/≤1.5kV

Certification

CE; RoHS

KEMA;CB;CE; RoHS

CE; RoHS

Follow current extinguishing
capability at Uc [If]

100Arms(N-PE)

Response time [tA](L-N/N-PE)

≤ 25ns/≤ 100ns

Max. back up fuse [F]

125A gL/gG

Operating temperature range [Tu]

-40°C...+80°C

Cross-sectional area

1.5mm2(16AWG) ~ 25mm2(4AWG) solid / 35mm2(2AWG) flexible

Mounting on

35mm DIN rail,EN 60715

Operating state / Failure indication 

Green:ok / Red: faulty 

Dimension 

4 mods (72mm wide) 

Enclosure material

Yellow & light gray (base) thermoplastic, UL94-V0

Compliance

 IEC 61643-11:2011 ; EN 61643-11:2012; GB/T 18802.11-2020

Number of remote terminals

1(or Optional) 

Type of remote signaling contact

Switching contact

Switching capacity(UN/IN)

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;75V/0.5A

Cross-sectional area for remote signaling contact

Max. 1.5mm2 (16AWG)solid/flexible

12.jpg

 Application Scenarios

Pluggable SPD Class II for three-phase TT/TN-S (“3+1 circuit) power supply systems.

Hightlight Features

1. Pluggable module, easy for installation and maintenance.

2. High discharge capacity, quick response.

3. Double thermal disconnector devices, providing more reliable protection.

4. Green window will change when fault and also provide remote alarm control at the same time.

6. Suitable for use in three phase AC systems.

7. Suitable for TT/TN-S installations.

8. Crafted from selected flame-retardant enclosure, it effectively combats the spread of fire, buying critical time to protect life and property.

9. Powered by advanced European technology, it provides comprehensive and reliable protection for electrical equipment.

11.jpg18.jpg

Summary

Designed for installation in LPZ 1-2 or higher zones, this surge protection device safeguards low-voltage equipment from power surges and remote terminal is optional.

Application:Pluggable SPD Class II for three-phase TT/TN-S (“3+1 circuit) power supply systems.

Compliance Standards:IEC 61643-11:2011;EN 61643-11:2012;GB/T 18802.11-2020.

1.jpg

FAQ

 

 

 

 

 

 

GET IN TOUCH