Product Description

Surge Protection Device Data

Type

BT PCM TNS 275 RM

BT PCM TNS 320 RM

BT PCM TNS 385 RM

According to IEC 61643-11/EN 61643-11

Class II (class 2/C) / Type 2

System mode

3 Phase TNS System (“ 4+0 " circuit)

Nominal voltage  [UN](50/60Hz) 

230V/400V

230V/400V

230V/400V

Rated voltage (max. continuous voltage) [Uc] (50/60Hz)

275V

320V

385V

Nominal discharge current (8/20μs) [In] 

20kA

20kA

20kA

Max. discharge current (8/20μs) [Imax] 

40kA

40kA

40kA

Modules

4P

4P

4P

Voltage protection level at In [Up] 

≤ 1.3kV

 ≤ 1.5kV

≤ 1.8kV

Voltage protection level at 5kA [Up] 

≤ 1.0kV

≤ 1.2kV

≤ 1.35kV

Response time [tA] 

≤ 25ns

Max. back up fuse [F]

125A gL/gG

Operating temperature range [Tu] / Operating state / Failure indication 

-40°C...+80°C / Green / Red 

Cross-sectional area 

1.5mm2 ~ 25mm2 solid / 35mm2 flexible

Mounting on /  Number of remote terminals

35mm DIN rail / 1

Dimension /  Degree of Protection 

4 mods (72mm) / IP 20

Certification

KEMA-KEUR; CB; CE; RoHS

Warranty

3 Years

Type of remote signaling contact

Switching contact

Switching capacity a.c.

250V/0.5A

Switching capacity d.c.

250V/0.1A, 125V/0.2A, 75V/0.5A

Cross-sectional area for remote signaling contact

Max. 1.5mm2 solid/flexible

Ordering information

Type

BT PCM TNS 275 RM

BT PCM TNS 320 RM

BT PCM TNS 385 RM

Art.-No.

810834

810887

810835

Packing unit

1pc(s)

1pc(s)

1pc(s)

 142021

Surge Protection Device Features

•  Pluggable module, easy for installation and maintenance.

•  High discharge capacity, quick response.

•  Double thermal disconnector devices, providing more reliable protection.

•  Green window will change when fault and also provide remote alarm control at the same time.

•  Surge protection device has passed KEMA-KEUR certification.

Surge Protection Device Summary

BT PCM YNS 275 RM surge protection device is for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class II (Class C) for 3 Phase TNS("4+0 circuit) power supply system. Designed according to IEC 61643-11/EN 61643-11.

1BT PCM TNS 275 RM Surge Protection Device factoryBT PCM TNS 275 RM Surge Protection Device supplierBT PCM TNS 275 RM Surge Protection Device detailsBT PCM TNS 275 RM Surge Protection Device manufactureBT PCM TNS 275 RM Surge Protection Device manufactureFAQBT PCM TNS 275 RM Surge Protection Device details

 

 

 