Technical Data
Type |
BT PCM20 150 RM/2P |
BT PCM TN 150 RM |
BT PCM60 150 RM/2P |
BT PCM TN 275 RM |
Art.-No. |
810872 |
810844 |
810852 |
810845 |
Nominal a.c. voltage [UN] |
120V |
120V |
120V |
230V |
Rated voltage (max. continuous a.c. voltage) [Uc] |
150V |
150V |
150V |
275V |
Frequency[Hz] |
50/60 Hz |
50/60 Hz |
50/60 Hz |
50/60 Hz |
Nominal discharge current (8/20μs) [In] |
10kA |
20kA |
30kA |
20kA |
Max. discharge current (8/20μs) [Imax] |
20kA |
40kA |
60kA |
40kA |
Voltage protection level[Up] |
≤0.7kV |
≤0.9kV |
≤1.2kV |
≤1.3kV |
Certification |
CE;RoHS |
CE;RoHS;KEMA;CB |
CE; RoHS |
CE;RoHS;KEMA;CB |
Response time [tA] |
≤ 25ns |
|||
Max. back up fuse [F] |
125A gL/gG |
|||
Operating temperature range [Tu] |
-40°C...+80°C |
|||
Cross-sectional area |
1.5mm2(16AWG) ~ 25mm2(4AWG) solid / 35mm2(2AWG) flexible |
|||
Mounting on |
35mm DIN rail,EN 60715 |
|||
Operating state / Failure indication |
Green:ok / Red: faulty |
|||
Dimension |
2 mods (36mm wide) |
|||
Enclosure material |
Yellow & light gray (base) thermoplastic, UL94-V0 |
|||
Compliance |
IEC 61643-11:2011 ; EN 61643-11:2012; GB/T 18802.11-2020 |
|||
Number of remote terminals |
1(or Optional) |
|||
Type of remote signaling contact |
Switching contact |
|||
Switching capacity(UN/IN) |
AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;75V/0.5A |
|||
Cross-sectional area for remote signaling contact |
Max. 1.5mm2 (16AWG)solid/flexible |
Application Scenarios
Pluggable SPD Class II for single-phase TN (“2+0” circuit) power supply systems.
Highlight Features
1. Pluggable module, easy for installation and maintenance.
2. High discharge capacity, quick response.
3. Double thermal disconnector devices, providing more reliable protection.
4. Green window will change when fault and also provide remote alarm control at the same time.
5. Suitable for use in single phase AC systems.
6. Mode of protection:L-PE;N-PE.
7. Suitable for TN installations.
8. Crafted from selected flame-retardant enclosure, it effectively combats the spread of fire, buying critical time to protect life and property.
9. Powered by advanced European technology, it provides comprehensive and reliable protection for electrical equipment.
Summary
Designed for installation in LPZ 1-2 or higher zones, this surge protection device safeguards low-voltage equipment from power surges and remote terminal is optional.
Application:Pluggable SPD Class II for single-phase TN (“2+0” circuit) power supply systems.