Product Description

   Technical data

Type

BT PUM 4WY 208 RM/4P

BT PUM 4WY 480 RM/4P

 

BT PUM 4WY 600 RM/4P

 

UL1449 - SPD

Open-Type 1

System type

3 Phase Wye/4W+G

Nominal system a.c. voltage (50/60Hz)[UN] 

120V/208V

277V/480V

347V/600V

Max. continuous operating voltage AC [MCOV] 

(L-N)/(L-G)/(N-G)/(L-L)

180V / 360V/180V/360V

385V /565V/180V/ 770V

510V /690V/180V/ 1020V

Nominal discharge current (8/20µs) [In] 

20kA 

20kA 

20kA 

Max. discharge current (8/20µs) [Imax] 

50kA 

50kA 

50kA 

Lighting impulse current (10/350µs)

8kA

8kA

---

Voltage protection rating  [VPR] 

[L-N] / [L-G]

600Vpk / 1200Vpk/600Vpk

1200Vpk /1800Vpk/600Vpk 2500Vpk

1500Vpk/2000Vpk/600Vpk 3000Vpk

Short circuit current rating [SCCR] 

200kA

200kA

200kA

 Max. backup fuse [F]

125A gL/gG

Operating temperature range [Tu]  Operating state / Failure indication 

-35°C...+85°CGreen / Red 

Cross-sectional area

2.5mm2 ~ 25mm2 solid/flexible

Mounting on / Number of remote terminals

35mm DIN rail / 1

Enclosure material

Red module / light gray base, thermoplastic, UL 94-V0

Dimension Degree of Protection 

4 mods (72mm wide)  / IP 20

Test standards

IEC 61643-11; UL 1449-4th; GB/T 18802.11

Certification

CE (LVD, EMC); RoHS

Type of remote signaling contact Orientation for normal installation

Switching contact In door

Switching capacity a.c.

250V/0.5A

Switching capacity d.c.

250V/0.1A, 125V/0.2A, 75V/0.5A

Cross-sectional area for remote signaling contact

Max. 1.5mm2 solid/flexible

Ordering information

Type

BT PUM 4WY 208 RM/4P

BT PUM 4WY 480 RM/4P

BT PUM 4WY 600 RM/4P

Art.-No.

815 091

815 095

815 097

Packing unit

1pc(s)

1pc(s)

1pc(s)

 

 Image_BT PUM 4WY 600 RM_4P.jpg

Dimension.jpgBT PUM 4WY 208.pngSystem.jpg

 

 
 

Hightlight Features

•  Combined module SPD for 3 Phase Wye electrical systems (4W+G).  

•  Max. Discharge current (Imax) up to 50kA 8/20µs.

•  Short-circuit current rating (SCCR) 200kA.

•  Double thermal disconnector device, providing more reliable protection.

•  Green window will change when fault and also provide remote alarm control at the same time.

 