Technical data
|
Type |
BT PUM 4WD 240 RM/4P |
BT PUM 4WD 480 RM/4P |
|
UL1449 - SPD |
Open-Type 1 |
|
|
System type |
3 Phase High Leg / 4W+G |
|
|
Nominal system AC voltage (50/60Hz) [UN] |
120V/240V Delta |
240V/480V Delta |
|
Max. continuous operating voltage AC [MCOV] (L-N)/(L-G)/(N-G)/(L-L)/(H-N)/(H-G)/(L-H) |
230V/410V/180V/460V/275V/455V/505V |
385V /565V/180V/ 770V/510V/690V/895V |
|
Nominal discharge current (8/20µs) [In] |
20kA |
20kA |
|
Max. discharge current (8/20µs) [Imax] |
50kA |
50kA |
|
Lighting impulse current (10/350µs) |
8kA |
-- |
|
Voltage protection rating [VPR] (L-N)/(L-G)/(N-G)/(L-L)/(H-N)/(H-G)/(L-H) |
0.7kVpk /1.2kVpk/0.6kVpk/1.5kVpk/0.8kVpk/1.5kVpk /1.5kVpk |
1.2kVpk/1.8kVpk/0.6kVpk/2.5kVpk/1.5kVpk/2.0kVpk/2.5kVpk |
|
Short circuit current rating [SCCR] |
200kA |
200kA |
|
Max. backup fuse [F] |
125A gL/gG |
|
|
Operating temperature range [Tu], Operating state / Failure indication |
-35°C...+85°C, Green / Red |
|
|
Cross-sectional area |
2.5mm2 ~ 25mm2 solid/flexible |
|
|
Mounting on / Number of remote terminals |
35mm DIN rail / 1 |
|
|
Enclosure material |
Red module / light gray base, thermoplastic, UL 94-V0 |
|
|
Dimension / Degree of Protection |
4 mods (72mm wide) / IP 20 |
|
|
Test standards |
IEC 61643-11; UL 1449-4th; GB/T 18802.11 |
|
|
Certification |
CE (LVD, EMC); RoHS |
|
|
Type of remote signaling contact / Orientation for normal installation |
Switching contact / In door |
|
|
Switching capacity a.c. |
250V/0.5A |
|
|
Switching capacity d.c. |
250V/0.1A, 125V/0.2A, 75V/0.5A |
|
|
Cross-sectional area for remote signaling contact |
Max. 1.5mm2 solid/flexible |
|
|
Ordering information |
||
|
Type |
BT PUM 4WD 240 RM/4P |
BT PUM 4WD 480 RM/4P |
|
Art.-No. |
815 083 |
815 088 |
|
Packing unit |
1pc(s) |
1pc(s) |



Hightlight Features
• Combined module SPD for 3 Phase High Leg Delta electrical systems(4W+G circuit) .
• Max. Discharge current (Imax) up to 50kA 8/20μs.
• Short-circuit current rating (SCCR) 200kA.
• Double thermal disconnector device, providing more reliable protection.
• Green window will change when fault and also provide remote alarm control at the same time.
Summary
BT PUM 4WD 480 RM/4P(815088) Surge protector Device is mainly used in the main distribution system, provide the best protection as they designed to protecting low voltage equipment against indirect surges with ensuring a low protection level (VPR).
Application in AC voltage system of 3 Phase High Leg Delta electrical systems(4W+G circuit), for example, computer, communication, or control equipment. Designed according to IEC 61643-11 and UL 1449-4th type 4-1 combined SPD Modules.








EN
AR
BG
HR
CS
DA
NL
FI
FR
DE
EL
HI
IT
JA
KO
NO
PL
PT
RO
RU
ES
SV
CA
TL
IW
ID
LV
LT
SR
SK
SL
UK
VI
SQ
ET
GL
HU
MT
TH
TR