Telebahn 240V 254V 277V 385V AC 20kA 50kA 8kA 200kA Single Phase Surge Protector Protective Suppression SPD
- Overview
- Inquiry
- Related Products
Technical data
Type |
BT PUM S 120 RM/1P |
BT PUM S 240 RM/1P |
BT PUM S 347 RM/1P |
UL1449 - SPD |
Open-Type 1 |
||
System type |
Single Phase |
||
Nominal system voltage (50/60Hz) [VAC] [L-N] / [L-G] |
120V or 127V |
240V or 254V or 277V |
347V |
Max. continuous operating voltage AC [MCOV] [L-N] / [L-G] |
230V |
385V |
510V |
Nominal discharge current (8/20µs) [In] |
20kA |
20kA |
20kA |
Max. discharge current (8/20µs) [Imax] |
50kA |
50kA |
50kA |
Lighting impulse current (10/350µs) |
8kA |
8kA |
--- |
Voltage protection rating [VPR] [L-N] / [L-G] |
700Vpk |
1200Vpk |
1500Vpk |
Short circuit current rating [SCCR] |
200kA |
200kA |
200kA |
Max. backup fuse [F] |
125A gL/gG |
||
Operating temperature range [Tu] , Operating state / Failure indication |
-35°C...+85°C, Green / Red |
||
Cross-sectional area |
2.5mm2 ~ 25mm2 solid/flexible |
||
Mounting on / Number of remote terminals |
35mm DIN rail / 1 |
||
Enclosure material |
Red module / light gray base, thermoplastic, UL 94-V0 |
||
Dimension / Degree of Protection |
1 mod (18mm wide) / IP 20 |
||
Test standards |
IEC 61643-11; UL 1449-4th; GB/T 18802.11 |
||
Certification |
CE (LVD, EMC); RoHS |
||
Type of remote signaling contact / Orientation for normal installation |
Switching contact / In door |
||
Switching capacity a.c. |
250V/0.5A |
||
Switching capacity d.c. |
250V/0.1A, 125V/0.2A, 75V/0.5A |
||
Cross-sectional area for remote signaling contact |
Max. 1.5mm2 solid/flexible |
||
Ordering information |
|||
Type |
BT PUM S 120 RM/1P |
BT PUM S 240 RM/1P |
BT PUM S 347 RM/1P |
Art.-No. |
815 001 |
815 002 |
815 003 |
Packing unit |
1pc(s) |
1pc(s) |
1pc(s) |
Hightlight Features
• Combined module SPD for Split Phase electrical systems with N wire protected.
• Max. Discharge current (Imax) up to 50kA 8/20μs.
• Short-circuit current rating (SCCR) 200kA.
• Double thermal disconnector device, providing more reliable protection.
• Green window will change when fault and also provide remote alarm control at the same time.
Summary
BT PUM S 240 RM/1P(815002) Surge protector Device is mainly used in the main distribution system, provide the best protection as they designed to protecting low voltage equipment against indirect surges with ensuring a low protection level (VPR).
Application in AC voltage system of Split Phase electrical systems with N wire protected, for example, computer, communication, or control equipment. Designed according to IEC 61643-11 and UL 1449-4th type 4-1 combined SPD Modules.