 Technical data

Type

BT P BCM 25 

(150 ) RM /3+N

BT P BCM 25 

(255) RM /3+N

BT P BCM 25 

(320) RM/3+N

Rated voltage (max. continuous voltage) [Uc]

 (L-N/N-PE)

150V/255V

255V/255V

320V/255V

Total lightning impulse current (10/350) [Iimp] (L1+L2+L3+N-PE)

100kA

100kA

100kA

Lightning impulse current (10/350) [Iimp] 

(L-N/N-PE)

25kA/75kA

25kA/75kA

25kA/75kA

Nominal discharge current (8/20) [In] 

(L-N/N-PE)

50kA/100kA

50kA/100kA

50kA/100kA

Voltage protection level at In [Up] 

≤ 1.5kV

≤ 1.5kV

≤ 1.5kV

Response time [tA] 

≤ 100ns

≤ 100ns

≤ 100ns

Follow current extinguishing capability at Uc 

32A fuse will not be triggered at 2kArms 255V

Max. back up fuse (L) [F]

200A gL/gG

Max. back up fuse (L-L) [F]

125A gL/gG

Operating temperature range [Tu]

-40°C...+80°C

Min. cross-sectional area

10mm2 solid / flexible

Max. cross-sectional area

35mm2 solid / 50mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Purple (module) & light grey (base) thermoplastic, UL94-V0

Dimension

8 mods

Test standards

IEC 61643-1; EN 61643-1; GB 18802.1

Certification

CE, CB, Rohs, ISO9001:2015

Type of remote signalling contact

Switching contact





Image_BT P BCM 25 RM_ 3+N.jpg

Hightlight Features

  10/350μs, 8/20μs sparkgap. 

  Three-phase lightning current surge arrester, Pluggable.

  Lightning impulse current withstand max.25kA (10/350μs) L-Nmax.50kA (10/350μs) N-PE.

  Adopt hermetical GDT technology, high follow current extinguishing capacity.

  Extremely low voltage protection level.

  Double thermal disconnector devices, providing more reliable protection.

 

Summary

 for installation at LPZ 0A-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I (Class B) for TT (3+1 circuit) and TNS power supply system. Designed according to IEC 61643-11/GB 18802.1.

5.jpg