Technical data

 

Combined  Type

BT BCM 50 RM/1+N

Single module

BT BCM 50 RM (*1P)

BT BNM 100 (*1P)

 Nominal voltage a.c.  [ UN ]

230V

Total lightning impulse current (10/350) [ Iimp ]

[L+N - PE]

100kA

Rated voltage (max. continuous a.c. voltage) [ Uc ]

[L-N / N-PE]

255V

255V

Lightning impulse current (10/350) [ Iimp ]

[L-N / N-PE]

50kA

100kA

Nominal discharge current (8/20) [ In ]

[L-N / N-PE]

50kA

100kA

Max. discharge current (8/20) [ In ]

[L-N / N-PE]

100kA

200kA

Voltage protection level at In [ Up ]

[L-N / N-PE]

≤ 1.8kV

≤ 1.5kV

Follow current extinguishing capability at Uc [ If ]

[L-N / N-PE]

32A fuse will not be triggered at 10kArms 255V

100Arms

Response time [tA]

[L-N / N-PE]

≤ 25ns

≤ 100ns

TOV voltage [UT]

[L-N / N-PE]

355V / 5sec

1200V / 200ms

Max. back up fuse (L) [F]

200A gL/gG

Max. back up fuse (L-L') [F]

125A gL/gG

Operating temperature range [Tu]

-40°C...+80°C

Min. cross-sectional area

10mm2 solid / flexible

Max. cross-sectional area

35mm2 solid / 50mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Light grey thermoplastic, UL94-V0

Dimension

4 mods

Test standards

IEC 61643-1; EN 61643-1

Certification

CE, RoHS, ISO9001:2015

Type of remote signalling contact

Switching contact

---

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

---

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

---

Ordering information

Type

BT BCM 50 RM/1+N

Art.-No.

801 015

Packing unit

1pc(s)

Image_BT BCM 50 RM_1+N.jpgDimension_BT BCM 50 RM_1+N.jpgBT BCM 50 RM 1+N.png

Hightlight Features

  10/350μs, 8/20μs sparkgap, single-phase lightning surge arrester.

  Lightning impulse current withstand max.50kA (10/350μs) L-N,max.100kA (10/350μs) N-PE.

  Adopt hermetical GDT technology, high follow current extinguishing capacity.

  Extremely low voltage protection level.

  Double thermals for parallel or series (V-shape) connection.

  Multifunctional connection for conductors and busbars.

  Green light indicates functional mode (L-N).

Application environment

•  Temperature: -40°C ~ +80°C  

•  Relative humidity:  ≤ 95% (25°C)

Summary

BT BCM 50 RM/1+N is for installation at LPZ 0A-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I (Class B) for TN and TT (1+1 circuit)  power supply system. mainly used in power supply system such as power distribution room, distribution cabinet and other important power supply system. Designed according to IEC 61643-11/EN 64643-11. 