- Overview
- Inquiry
- Related Products


Technical Data
|
Type |
BT P C 4P 385 RM |
|
According to IEC 61643-11/EN 61643-11 |
Class II (class 2/C) / Type 2 |
|
Art.-No. |
810143 |
|
Nominal a.c. voltage[UN](50/60 Hz) |
230V/400V |
|
System protection mode |
TNC-S and TN-S |
|
Rated voltage(max. continuous a.c. voltage) [ Uc ](50/60Hz) |
385V |
|
Nominal discharge current(8/20) [ In ] |
20kA |
|
Nominal discharge current(8/20) [ Imax ] |
40kA |
|
Voltage protection level at 5kA [ Up ] |
≤ 1.35kV |
|
Voltage protection level at In [ Up ] |
≤ 1.8kV |
|
Response time [ tA ] |
≤ 25ns |
|
TOV voltage[ UT] |
385V/5sec |
|
Max. Back up fuse(L) |
125A gL/gG |
| Operating temperature range [Tu] |
-40°C...+80°C |
| Degree of protection |
IP20 |
|
Cross-section area |
1.5mm2 -25mm2 (solid)/ 35mm2 (flexible) |
|
Mounting on |
35mm DIN rail, EN 60715 |
|
Place of installation |
Indoor |
|
Number of Remote Terminal |
1(or Optional) |
|
Enclosure material |
Purple (Gray/Black module,Optional) thermoplastic, UL94-V0 |
|
Dimension |
4 mods (72mm wide) |
|
Test standards |
IEC 61643-11:2011 ; EN 61643-11:2012; GB/T 18802.11-2020 |
|
Certification |
CE (LVD, EMC); RoHS |
|
Type of remote signalling contact |
Switching contact |
|
Switching capacity a.c |
AC: 250V/0.5A |
|
Switching capacity d.c |
DC: 250V/0.1A; 150V/0.2A; 750V/0.5A |
|
Cross-sectional area for remote signalling contact |
Max 1.5mm2 (solid/flexible) |

Hightlight Features

Summary
BT P C 4P 385 RM(810143) is for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class II (Class C) for three phase TNC-S and TN-S(“4+0” circuit) power supply system. Designed according to IEC 61643-11:2011 ; EN 61643-11:2012; GB/T 18802.11-2011.