Technical data
Type |
BT PVM 1200 RM/2P |
Nominal d.c. (PV) voltage [UN] |
1200V |
Short-circuit current rating [ ISCPV ] |
1kA |
Max continuous d.c. voltage [Uc] |
1320V |
Total discharge current (8/20) [ In total] |
40kA |
Nominal discharge current (8/20) [In] |
20kA |
Max. discharge current (8/20) [Imax] |
40kA |
Voltage protection level at In [Up] |
≤ 4.5kV |
Voltage protection level at 5kA [Up] |
≤ 3.5kV |
Response time [tA] |
≤ 25ns |
Operating temperature range [Tu] |
-40°C...+80°C |
Cross-sectional area |
1.5mm2 ~ 25mm2 solid / flexible |
Mounting on |
35mm DIN rail |
Enclosure material |
Purple (module) / Light grey (base) thermoplastic, UL94-V0 |
Dimension |
2 mods (36mm) |
Test standards |
IEC 61643-11; EN 61643-11; GB 18802.11;EN 50539-11 |
Certification |
CE (LVD, EMC); RoHS |
Type of remote signalling contact |
Switching contact |
Switching capacity a.c. |
AC:250V/0.5A |
Switching capacity d.c. |
DC:250V/0.1A;150V/0.2A;750V/0.5A |
Cross-sectional area for remote signalling contact |
Max. 1.5mm2 solid / flexible |
Ordering information |
|
Type |
BT PVM 1200 RM/2P |
Art.-No. |
800 513 |
Packing unit |
1pc(s) |
Summary
BT PVM 1200 RM/2P is for max. dc voltage 1200V system and applied in photovoltaic system, protecting photovoltaic generator and inverter and so on. Designed according to IEC 61643-11 / EN 61643-11.
Hightlight Features
• Pluggable module, High discharge capacity, quick response.
• Approved fault-resistant circuit Y-circuit, consist of two varistors and thermal disconnection device.
• Integrated DC fuse allows safe replacement of protection modules without arc formation.
• Double thermal disconnector devices, providing more reliable protection.
• Green windows will change when fault occurs, also provide remote alarm control at the same time.