All Categories
Measuring & Controlling System SPD

Measuring & Controlling System SPD

24V 4 Signal Lines SPD Surge Protection Device for Data Transmission

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description

2.jpg

 

2.png

Technical Data

Type

BS RMT-TTY 24

Art.-No.

650401

Nominal voltage [UN]

24V

Rated voltage (max. continuous d.c. voltage) [Uc]

26.8V

Rated voltage (max. continuous a.c. voltage) [Uc]

18.9V

Nominal current [IL]

0.1A

Nominal discharge current (8/20μs)[In]

10kA

Voltage protection level at In[Up]

≤ 65V(line-line),  ≤ 700V(line-PG)   

Voltage protection level at 1kV/us[Up]

≤ 36V(line-line),  ≤ 700V(line-PG)   

Transmission frequency

10MHz(line-line)

Capacitance[C]

≤ 1pF(line-line) 

Response time[tA]

≤ 1ns(line-line),  ≤ 100ns(line-PG)   

Degree of protection

IP 20

Operating temperature range [Tu]

-40°C...+80°C

Series impedance per line[R]

2.2Ω

Place of installation

Indoor

Cross-sectional area

Max. 1.5mm2 soild/ flexible

Shield earthing

Indirectly via integrated spark gap

Earthing via

Outgoing cable 1.5mm2 x300mm

Housing

Auminum

Test standards

IEC 61643-21; EN 61643-21; GB 18802.21

Certification

CE; RoHS

Warranty

3 Years

 

.png 

Hightlight Features

1. For protecting 4 signal lines data transmission system.
2. Quick response, low voltage protection level.
3. Wall mounting on, direct shield earthing.

 

Application

 

BS RMT-TTY 24 is for two twisted pairs signal protection in data transmission devices.

Application environment

1. Temperature: -40°C~ +80°C

2. Relative humidity: ≤ 95% (25°C)

Summary

BS RMT-TTY 24 (650401) is designed for installation at location zones 0B-2 and higher interfaces, or directly near the protected equipment. It provides reliable surge protection for data transmission devices with 4 signal lines. The device is engineered in compliance with IEC 61643-21, EN 61643-21, and GB/T 18802.21 standards.