- Overview
- Inquiry
- Related Products
Technical data
Type |
BT PVM 1000 2P RM/EPB 1X 2-2 32A |
Art.-No. |
800598 |
According to IEC 61643-11; EN 61643-11; EN 50539-11; IEC 61643-31 |
Class II / Type 2 |
PV system protection modules SPD type |
DC Modules: BT PVM 1000 RM/2P |
Nominal d.c. (PV) voltage [UN] |
1000V |
Single Pole Max continuous d.c. voltage [Uc] |
1060V |
Short-circuit current rating [ ISCPV ] |
1000A |
Nominal discharge current (8/20µs) [In](DC+/DC- – PE ) |
20kA |
Max. discharge current (8/20µs) [Imax](DC+/DC- – PE ) |
40kA |
Voltage protection level at In [Up] |
≤ 4.0kV |
Response time [tA](DC+/DC- – PE ) |
≤ 25ns |
Built-in DC fuse(1000VDC) |
15A(10x38) |
Circuit breaker(MCB) |
C32(1000VDC) |
PV insulating enclosure |
IP65 waterproof (12 modules DIN) |
Operating temperature range [Tu] |
-40°C...+80°C |
Cross-sectional area |
1.5mm2 ~ 25mm2 solid / 35mm2 flexible |
Mounting on |
Wall installation(screws) |
Enclosure material |
Light grey thermoplastic, UL94-V0 |
Test standards |
IEC 61643-11; EN 61643-11; GB 18802.11;EN-50539-11; IEC 61643-31 |
Certification |
CE (LVD, EMC); RoHS;REACH |
Type of remote signalling contact |
Switching contact |
Switching capacity a.c. |
AC:250V/0.5A |
Switching capacity d.c. |
DC:250V/0.1A;150V/0.2A;750V/0.5A |
Cross-sectional area for remote signalling contact |
Max. 1.5mm2 solid / flexible |
Hightlight Features
1. Adopting PV SPD DC modules type 2 (class II) for protecting PV system.
2. Single-pole module max. lightning discharge current up to 20kA (8/20us).
3. Built-in circuit breaker, prewired with SPD, easy for installation.
4. With the 2-input connected and 2-output connected of PV-MC4 ports interface.
5. Dual arc-extinguishing protection device, providing full protection against fire hazards for equipment.
6. Integrated DC-fuse allows safe replacement of protection modules without arc formation.
7. Green window will change when fault and also provide remote alarm control at the same time.
8. Advanced Western European technology guarantees ultra-reliable PV surge protection.
9. Water proof level lP65, suitable for outdoor PV solar application.
Summary
Photovoltaic Surge Protection Box BT PVM 1000 2P RM/EPB 1X 2-2 32A(800598) is combined DC MCB and PV SPD modules surge protection box, applied in photovoltaic system. Design the max. PV voltage max. up to 1000V DC SPD for protecting photovoltaic inverter from surge damages. Compliance Standards: IEC 61643-11:EN 61643-11: GBT 18802.11: IEC 61643-31 and EN 50539-11.
Other
As China's first batch surge protection device manufacturer, we are committed to producing high-quality surge protection device while providing customized solutions for global industry leaders for over 30 years. Welcome OEM and ODM!