- Overview
- Inquiry
- Related Products
Technical Data
Type |
BT TT 275 3N RM |
According to EN 61643-11, IEC 61643-11 |
Type3 / Class III |
Art.No. |
812330 |
Nominal a.c. voltage [UN] |
230V/400V( 50/60Hz ) |
Rated voltage (max. continuous a.c. voltage) [Uc] |
275V/440V( 50/60Hz ) |
Nominal current [IL] |
25A |
Nominal discharge current (8/20μs)(L-N) [In] |
5kA |
Nominal discharge current (8/20μs)(L+N-PE) [In] |
5kA |
Nominal discharge current (8/20μs)[L-N] [Imax] |
10kA |
Nominal discharge current (8/20μs)(L+N-PE) [Imax] |
10kA |
Combination wave(1.2/50)[Uoc] |
10kV |
Voltage protection level (L-N) [Up] |
≤ 0.95kV |
Voltage protection level (L/N-PE) [Up] |
≤ 1.5kV |
Response time(L-L) [tA] |
≤ 25ns |
Response time(L-PE) [tA] |
≤ 100ns |
Max. back up fuse [F] |
25A gL/gG |
Short circuit withstand capability at max. back up fuse |
6kArms |
Operating temperature range [Tu] |
-40°C...+80°C |
Degree of Protection |
IP 20 |
Cross-sectional area |
0.5mm2 ~ 6mm2 solid / 4mm2 flexible |
Number of remote terminals |
1(or Optional) |
Mounting on / Orientation for normal installation / Remote terminal |
35mm DIN rail,EN 60715 |
Enclosure material | Purple thermoplastic, UL94-V0 |
Dimension |
Three-phase,3mods |
perating state / Failure indication |
Green / Red |
Certification |
CE(LVD,EMC), RoHS |
Type of remote signalling contact |
Break contact |
Switching capacity[a.c.] |
250V/0.5A |
Swithcing capacity[d.c.] |
250V/0.1A; 125V/0.2A;75V/0.5A |
Cross-sectional area for remote signaling contact |
Max. 16AWG/1.5mm2 solid/flexible |
Highlight Features
1. Green light indicates normal and red indicates fault.
2. Three phase protection and with thermal diaconnectors.
3.Remote signalling connector for fault indication.
Summary
Surge Protective Device Type 3 BT TT 275 3N RM(812330)is for installation at LPZ 1-2 or higher, protecting low voltage equipment from surge damage and remote terminal is optional. Applied in modular SPD Class III (Class D) for three phase TT/TN-S("3+1" circuit) power supply system. Designed according to IEC 61643-11/ EN 61643-11 / GB / T 18802.11.