- Overview
- Inquiry
- Related Products
Technical Data
Type |
BS LSA 10G 110 |
Art.-No. |
660001 |
Nominal DC voltage[UN] |
110V |
Rated voltage(max. continuous d.c. voltage) [Uc] |
180V |
Rated voltage(max. continuous a.c. voltage) [Uc] |
127V |
Lightning impulse current (10/350μs) [Iimp] |
1kA |
Nominal discharge current (8/20μs) (per line) [In] |
10kA |
Voltage protection level at 1kV/us (line-line)[Up] |
≤ 600V |
Voltage protection level at 1kV/us (line-PG)[Up] |
≤ 600V |
Capacitance(line-line) [C] |
≤ 5pF |
Capacitance(line-PG) [C] |
≤ 5pF |
Response time (line-line) [tA] |
≤ 100ns |
Response time (line-PG) [tA] |
≤ 100ns |
Operating temperature range [Tu] |
-40°C...+80°C |
Pluggable into |
LSA-PLUS disconnection block |
Earthing via |
Earthing busbar |
Enclosure material |
Gray thermoplastic, UL94-V0 |
Test standards |
IEC 61643-21; EN 61643.21; GB 18802.21 |
Certification |
CE, RoHS, ISO9001:2015;REACH |
Hightlight Features
1. Mounting rail, for installing gas discharge tube.
2. High discharge capacity.
3. For installing at LPZ 0B-1 or higher boundary.
4. LSA-PLUS disconnection block.
Application
BS LSA 10G 110 is mainly used for telephone system or measurement and control system installing gas discharge tube.
Summary
BS LSA 10G 110 consists of one block mounting rail, one transparent cover and twenty gas discharge tubes.