Technical Data

Type

BT D 275 LED HS

Nominal voltage [UN](50/60Hz)

220V, 230V

Rated voltage (max. continuous d.c. voltage) [Uc](L-N / N-PE)(50/60Hz)

275V / 255V

Nominal discharge current (8/20μs) [In] 

10kA

Nominal discharge current (8/20μs) [Imax]

20kA

Nominal current [IL]

10A

Combination wave [Uoc]

20kV

Voltage protection level(L-N)[Up]

≤ 1.0kV

Voltage protection level(N-PE)[Up]

≤ 1.5kV

Follow current extinguishing capability at Uc(N-PE)[If]

                                                                     100Arms

Response time(L-N, L/N-PE)(TA)

 

≤ 25ns / ≤ 100ns

 

 

Max. backup fuse

16A gL/gG

Short withstand capability at max. backup fuse

       10kArms, 8/20μs 

TOV voltage(L-N, N-PE)

335V/5sec

1200V/200ms

Operating temperature range [Tu]

-40°C...+80°C 

Waterproof protection level

IP 67

Terminal wires

6 lines,1.5 square millimeter solid,length 120mm

Mounting on

3xM4.5mm screws

Enclosure material

gray/purple themoplastic,UL94-V0

Dimension

55x45x18 mm(1 mod)

Warranty Period / Weight

3 Years / 70g

Class

T2+T3

Test standards

IEC 61643-11; EN 61643-11; GB/T 18802.11

Operating state / Failure indication

Green / Red 

Certification

CE, RoHS

Art.-No.

820624

Packing unit

1pc(s)

Summary

BT D 275 LED HS(820624) is Used for LED power source fine protection. Can be soldered with parallel connection on to the PCB (Printed Circuit Board) or onto the external power source of electronic equipment to protect from power surges. Designed according to IEC 61643-11 / EN 61643-11 / GB 18802.1 standard, applied in SPD Class II + III (ClassC+ D) for fine protection of electronic equipment. LED drivers etc.