SPD Surge Protector 5V/12V/24V/48V/60V/110V 0-20mA 4-20mA CE RoHS for Measuring and Controlling System Surge Protection Devices
- Overview
- Inquiry
- Related Products
Technical Data
Type |
BS LC 24 |
Nominal voltage [UN] |
24V |
Rated voltage (max. continuous d.c. voltage) [Uc] |
26V |
Rated voltage (max. continuous a.c. voltage) [Uc] |
19V |
Nominal current [IL] |
0.5A |
Lightning impulse current (10/350) (per line) [Iimp] |
2.5kA |
Lightning impulse current (10/350) (total) [Iimp] |
5kA |
Nominal discharge current (8/20) (per line) [In] |
10kA |
Total nominal discharge current (8/20) (total) [In] |
20kA |
Voltage protection level at Iimp (line-line) [Up] |
≤ 90V |
Voltage protection level at Iimp (line-PG) [Up] |
≤ 45V |
Voltage protection level at 1kV/μs (line-line ) [Up] |
≤ 70V |
Transmission frequency [fG] |
5.1MHz |
Voltage protection level at 1kV/μs (line-PG ) [Up] |
≤ 35V |
Series impedance per line[R] |
2.2 Ohm |
Capacitance (line-line) [C] |
≤ 0.7nF |
Capacitance (line-PG) [C] | ≤ 1.3nF |
Operating temperature range [Tu] |
-40°C...+80°C |
Response time(line-line)[TA]/Response time(line-PG)[TA] |
≤ 1ns/≤ 1ns |
Cross-sectional area |
0.08mm2-4mm2 solid/2.5mm2 flexible |
Mounting on |
35mm DIN rail |
Enclosure material |
Orange thermoplastic, UL94-V0 |
Test standards |
IEC 61643-21; EN 61643-21; GB 18802.21;TD/T 1542 |
Certification |
CE(LVD.EMC); RoHS |
Article number |
610005 |
Brand |
Telebahn |
Packing unit |
1pc(s) |
Summary
For installation at LPZ 0A-2 or higher, or directly at the upstream near the protected devices. Provide protection for measuring and controlling system, such as the field bus, input/output interface of the 0-20mA, 4-20mA control line.