All Categories
AC SPD Class II

AC SPD Class II

Power Surge Protective Device KEMA-KEUR 4P 150V/275V/320V/385V AC 20kA 40kA 65kA for TT and TNS Power System Lightning SPD T2

Inquiry
  • Overview
  • Inquiry
  • Related Products

 

Summary

BT PCM TT 3+1 150/275/320/385 RM for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class II (Class C) for TT(“3+1” circuit) and TNS power supply system. Designed according to IEC 61643-11/GB 18802.1.

Hightlight Features

•  Pluggable module, easy for installation and maintenance.

•  High discharge capacity, quick response.

•  Double thermal disconnector devices, providing more reliable protection.

•  Green window will change when fault and also provide remote alarm control at the same time.

•  BT PCM 150/275/320/385/255 RM, BT PCM TN 150/275/320/385 RM, BT PCM TT 1+1 150/375/320/385 RM, BT PCM TNC 150/275/320/385 RM, BT PCM TNS 150/275/320/385 RM, BT PCM TT 3+1 150/275/320/385 RM and this series of products have passed KEMA-KEUR certification.

  

Technical data

Type

BT PCM TT3+1

150 RM

BT PCM TT3+1

275 RM

BT PCM TT3+1

320 RM

BT PCM TT3+1

 385 RM

Rated voltage (max. continuous voltage) [Uc] L-N / N-PE

150V / 255V

275V/ 255V

320V / 255V

385V / 255V

Nominal discharge current (8/20) [In] L-N / N-PE

20kA / 40kA

20kA / 40kA

20kA / 40kA

20kA / 40kA

Max. discharge current (8/20) [Imax] L-N / N-PE

40kA / 65kA

40kA / 65kA

40kA / 65kA

40kA / 65kA

Voltage protection level at In [Up]

L-N / N-PE

≤ 0.9kV / ≤ 1.8kV

≤ 1.3kV / ≤ 1.8kV

≤ 1.5kV / ≤ 1.8kV

≤ 1.8kV / ≤ 1.8kV

Voltage protection level 5kA [Up]

L-N

≤ 0.7kV

≤ 1.0kV

≤ 1.2kV

≤ 1.35kV

Response time [tA]

L-N / N-PE

≤ 25ns / ≤ 100ns

≤ 25ns / ≤ 100ns

≤ 25ns / ≤ 100ns

≤ 25ns / ≤ 100ns

Max. back up fuse [F]

125A gL/gG

125A gL/gG

125A gL/gG

125A gL/gG

Operating temperature range [Tu]

-40°C...+80°C

Cross-sectional area

1.5mm2 ~ 25mm2 solid / 35mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Purple (module) & light grey (base) thermoplastic, UL94-V0

Dimension

4 mods

Test standards

IEC 61643-11; GB 18802.1; YD/T 1235.1

Certification

KEMA, CE, CB, ROHS

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Ordering information

Type

BT PCM TT3+1

150 RM

BT PCM TT3+1

275 RM

BT PCM TT3+1

320 RM

BT PCM TT3+1

385 RM

Art.-No.

810 812

810 813

810 913

810 815

Packing unit

1pc(s)

1pc(s)

1pc(s)

1pc(s)

 

8.jpgDimension.jpg

 