All Categories
SPD Box

SPD Box

120V/240V 150V/300V AC 8kA 20kA 50kA T1+T2 DPS Surge Protection Device for Split Phase/3W+G

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description

 3

4.jpg

Technical data

Type

BT 3L-WF MBC 150 2P

Art.-No.

840843

According to IEC 61643-11 / EN 61643-11;UL 1449-4th

 Class I + Class II / Type 1 + Type 2 

Built-in PCB SPD module 

BT PCB BCM 150 RM

Phase

Split Phase/3W+G

Nominal a.c. voltage [UN]

120V/240V

Rated a.c. voltage (max. continuous voltage) [Uc]

150V

Rated a.c. voltage (max. continuous voltage)(L-G)/(L-L) [MCOV]

150V/300V

Lightning impulse current (10/350μs) [Iimp

8kA

Nominal discharge current (8/20μs) [In

20kA

Max. discharge current (8/20μs) [Imax

50kA

Response time [tA

≤ 25ns

TOV voltage [UT]

335V/5sec

Voltage protection rating(L-G)/(L-L)[VPR]

600Vpk/1200Vpk

Short circuit current rating [Isccr

200kA

Max. back up fuse [F]

125A gL/gG

LED operating state / fault indication

Green:power; Red:faulty

Operating temperature range [Tu]

-40°C...+80°C

Cross-sectional area

1.5mm2 ~ 25mm2 solid / flexible

Waterproof protection

IP 65

Mounting on

Screws fixing

Enclosure material

 light gray plastic thermoplastic, UL94-V0/  transparent cover

Test standards

UL 1449-4thIEC 61643-11:2011 ; EN 61643-11:2012; GB/T 18802.11-2020

Certification

CE (LVD, EMC); RoHS

 

 .png

Hightlight Features

1. Adopting plug-in PCB SPD class I+II surge protection module.

2.  Visual protection status indication, and failure indication function.

3. IP65 waterproof protection, suitable for outdoor application. 

4.  Built-in wiring terminal, easy for connection.

5.  Total lightning impulse current up to 20kA 10/350 μs.

6. High discharge capacity,quick response.

7.Suitable for Split Phase/3W+G installations. 

Application environment
Temperature:-40°C~ +80°C
Relative humidity: ≤ 95% (25°C) 

 

Summary

BT 3L-WF MBC 150 2P(840843)is installed in LPZ 0A-2 boundary or higher, protecting low voltage equipment from surge damages. Applied in SPD Class l+ll (1+2/B+C) for split-phase/3W+G power supply system. Designed according to IEC 61643-11 and UL 1449-4th type 4-1 combined SPD device.

1FAQ

GET IN TOUCH