230V/400V/255V AC 4P TOV T1+T2 Iimp25kA/In50kA/Imax75kA for 3-phase TN-S ( 4+0 circuit) System Power SPD Lightning Protectors
- Overview
- Inquiry
- Related Products
Class I+II Lightning current Surge Protective Devices for Three-phase TN-S Power Supply System
Summary
For installation at LPZ 0A-1 or high, protecting low voltage equipment against lightning and surge damages. Specially designed for TN-S system. Applied in SPD Class Ⅰ (Class B) for various power supply system of lightning current surge protection. Designed according to GB 18802.1/IEC 61643-11.
Hightlight Features
• Combined lightning current arrester for 3-phase TN-S ( “4+0” circuit) system, Pluggable Iimp(10/350μs):25kA,In(8/20μs):50kA, Imax(8/20μs):75kA, Iimp(10/350μs)total 100kA.
• Adopt hermetical GDT technology, high follow current extinguishing capacity.
• Extremely low voltage protection level.
• Double thermal disconnector devices, providing more reliable protection.
• Green window will change to red when fault occurs, also provide remote alarm terminal at the same time.
Application Environment
Temperature:-40°C...+80°C
Relative humidity:≤95%(25°C)
Technical Data
Type |
BT P BCM 25 RM/4P |
Nominal a.c. voltage [UN] |
230V/400V~ |
Rated voltage (max. continuous voltage) [Uc] |
255V~ |
Total lightning impulse current (10/350) [Iimp] |
100kA |
Lightning impulse current (10/350) [Iimp] |
25kA |
Nominal discharge current (8/20) [In] |
50kA |
Max. discharge current (8/20) [Imax] |
75kA |
Voltage protection level at In [Up] |
≤ 1.5kV |
Response time [tA] |
≤ 100ns |
Follow current extinguishing capability at Uc |
32A fuse will not be triggered at 2kArms 255V |
Max. back up fuse (L) [F] |
200A gL/gG |
Max. back up fuse (L-L’) [F] |
125A gL/gG |
TOV voltage |
335V/5sec |
Min. cross-sectional area |
10mm2 solid / flexible |
Max. cross-sectional area |
35mm2 solid / 50mm2 flexible |
Mounting on |
35mm DIN rail |
Enclosure material |
Purple (module) & light grey (base) thermoplastic, UL94-V0 |
Dimension |
8 mods (144mm) |
Test standards |
IEC 61643-11; EN 61643-11; GB/T 18802.11 |
Certification |
CE (LVD, EMC); RoHS |
Type of remote signalling contact |
Switching contact |
Switching capacity |
AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A |
Cross-sectional area for remote signalling contact |
Max. 1.5mm2 solid / flexible |
Ordering information |
|
Type |
BT P BCM 25 RM/4P |
Art.-No. |
800 914 |
Packing unit |
1pc(s) |