- Overview
- Inquiry
- Related Products
Ethernet Surge Protector POE Technical Data
Type / Application |
BS RJ45G 48(A) (Ethernet Surge Protector POE) |
Nominal voltage [UN] |
48V |
Rated voltage (max. continuous d.c. voltage) [Uc] |
48V |
Rated voltage (max. continuous a.c. voltage) [Uc] |
34V |
Max. continuous d.c. voltage (pair-pair POE) [Uc] |
57V |
Nominal current [IL] |
1A |
Lightning impulse current (10/350μs) (L-PG) [Iimp] |
0.5kA(Also passed 1kA) |
Nominal discharge current (8/20μs) (L-PG) [In] |
2.5kA |
Total nominal discharge current (8/20μs) (L-PG) [In] |
10kA |
Voltage protection level at In (L-L) [Up] |
≤ 190V |
Voltage protection level at In (L-PG) [Up] |
≤ 600V |
Voltage protection level at In (L-L POE) [Up] |
≤ 600V |
Nominal discharge current(8/20μs)(line-line)[In] |
150A |
Insertion loss at 250MHz |
≤ 2dB |
Capacitance (L-L) [C] |
≤ 165pF |
Capacitance (L-PG) [C] |
≤ 255pF |
Max. data transmission rates [Vs] |
> 1000Mbits/s |
Operating temperature range [Tu] / Degree of protection |
-40°C...+80°C / IP 20 |
Connection input/output |
RJ45 shield socket |
Pinning |
1/2, 3/6, 4/5, 7/8 |
Mounting on |
35mm DIN rail, According to EN 60715 |
Enclosure material / Number of Ports |
Auminum Enclosure / 1 Port |
Earthing via / Place of installation |
Earthing screw / Indoor |
Shield earthing |
Indirectly via integrated spark gap |
Nominal discharge current(8/20μs)(pair-pair POE)[In] |
150A |
Test standards |
IEC 61643-21; EN 61643-21; GB 18802.21 |
Certification |
CE(LVD,EMC), RoHS,REACH(Test report) |
Ordering information |
|
Type |
BS RJ45 G48(A) |
Art.-No. |
630 014 |
Packing unit |
1pc(s) |
Surge Protection Device(SPD) Features
1. For mounting on the 35mm DIN rail.
2. Max. continuous d.c. voltage Uc=57V, up to PoE++/4PPoE.
3. Good discharge capacity, low voltage protection level.
4.Quick response, high transmission speed, low signal attenuation.
5. Metallic housing RJ45 connection, easy for installation.
Summary
BS RJ45G 48(A)(630014) Ethernet Surge Protector POE Device is for Installation at LPZ 0B-2 or higher, directly installed in the front near the equipment; according to IEC standard for CAT6 or IEEE 802.3at or Class E integrated wiring system; all the industrial Ethernet 10M, 100M, 1000M or higher network surge protection; the nominal current, continuous DC high voltage, to support the PoE network with power supply system. This surge protector device use RJ45 interface protected by four pairs lines. Designed according to IEC 61643-21; EN 61643-21; GB/T 18802.21.