All Categories
SPD Box

SPD Box

Telebahn T1 for 3-phase TT ( 3+1 circuit)/TN-S System SPD for Black Panel Surge Arresters Box

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description

 1.jpg2.jpg

Summary

  Adopting lightning current Class I+II SPD, it has hermetical GDT technology to combine "3+1" or "4+0" circuit, applied in three-phase TT or TN-S power supply system. Generally installing in door main distribution panel or cabinet. Designed according to IEC 61643-11; GB/T 18802.11.

Technical data

Type

BT 5L BCM 255/100 3+1

Nominal a.c. voltage [UN]

230V/400V~

Rated voltage (max. continuous voltage) [Uc]

255V~

Total lightning impulse current (10/350) [Iimp](L1+L2+L3+N-PE) 

100kA

Lightning impulse current (10/350) [Iimp] 

L-N:25kA N-PE:50kA

Nominal discharge current (8/20) [In] 

50kA

Max. discharge current (8/20) [Imax] 

75kA

Voltage protection level at In [Up] 

L-N:≤ 1.8kV N-PE: 1.5kV

Response time [tA] 

100ns

Follow current extinguishing capability at Uc 

32A fuse will not be triggered at 2kArms 255V

Max. back up fuse (L) [F]

200A gL/gG

Max. back up fuse (L-L) [F]

125A gL/gG

TOV voltage

335V/5sec

Min. cross-sectional area

10mm2 solid / flexible

Max. cross-sectional area

35mm2 solid / 50mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Purple (module) & light grey (base) thermoplastic, UL94-V0

Dimension

8 mods (144mm)

Test standards

IEC 61643-11; EN 61643-11; GB/T 18802.11; TD/T 1235.1

Certification

CE (LVD, EMC); RoHS

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Ordering information

Type

BT 5L BCM 255/100 3+1

Art.-No.

800 914

Packing unit

1pc(s)

 

17.jpg18.jpgFAQ


 

 

 