All Categories
AC SPD Class II

AC SPD Class II

Power Surge Protective Device KEMA-KEUR 4P 150V/275V/320V/385V AC 20kA 40kA 65kA for TT and TNS Power System Lightning SPD T2

Inquiry
  • Overview
  • Inquiry
  • Related Products

 

Summary

BT PCM TT 3+1 150/275/320/385 RM for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class II (Class C) for TT(“3+1” circuit) and TNpower supply system. Designed according to IEC 61643-11/GB 18802.1.

Hightlight Features

  Pluggable module, easy for installation and maintenance.

  High discharge capacity, quick response.

  Double thermal disconnector devices, providing more reliable protection.

  Green window will change when fault and also provide remote alarm control at the same time.

•  BT PCM 150/275/320/385/255 RM, BT PCM TN 150/275/320/385 RM, BT PCM TT 1+1 150/375/320/385 RM, BT PCM TNC 150/275/320/385 RM, BT PCM TNS 150/275/320/385 RM, BT PCM TT 3+1 150/275/320/385 RM and this series of products have passed KEMA-KEUR certification.

  

Technical data

Type

BT PCM TT3+1

150 RM

BT PCM TT3+1

275 RM

BT PCM TT3+1

320 RM

BT PCM TT3+1

 385 RM

Rated voltage (max. continuous voltage) [Uc] L-N / N-PE

150V / 255V

275V/ 255V

320V / 255V

385V / 255V

Nominal discharge current (8/20) [In] L-N / N-PE

20kA / 40kA

20kA / 40kA

20kA / 40kA

20kA / 40kA

Max. discharge current (8/20) [Imax] L-N / N-PE

40kA / 65kA

40kA / 65kA

40kA / 65kA

40kA / 65kA

Voltage protection level at In [Up]

L-N / N-PE

≤ 0.9kV / ≤ 1.8kV

≤ 1.3kV / ≤ 1.8kV

≤ 1.5kV / ≤ 1.8kV

≤ 1.8kV / ≤ 1.8kV

Voltage protection level 5kA [Up]

L-N

≤ 0.7kV

≤ 1.0kV

≤ 1.2kV

≤ 1.35kV

Response time [tA]

L-N / N-PE

≤ 25ns / ≤ 100ns

≤ 25ns / ≤ 100ns

≤ 25ns / ≤ 100ns

≤ 25ns / ≤ 100ns

Max. back up fuse [F]

125A gL/gG

125A gL/gG

125A gL/gG

125A gL/gG

Operating temperature range [Tu]

-40°C...+80°C

Cross-sectional area

1.5mm2 ~ 25mm2 solid / 35mm2 flexible

Mounting on

35mm DIN rail

Enclosure material

Purple (module) & light grey (base) thermoplastic, UL94-V0

Dimension

4 mods

Test standards

IEC 61643-11; GB 18802.1; YD/T 1235.1

Certification

KEMA, CE, CB, ROHS

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Ordering information

Type

BT PCM TT3+1

150 RM

BT PCM TT3+1

275 RM

BT PCM TT3+1

320 RM

BT PCM TT3+1

385 RM

Art.-No.

810 812

810 813

810 913

810 815

Packing unit

1pc(s)

1pc(s)

1pc(s)

1pc(s)

 

8.jpgDimension.jpg

 

9.jpg 

1FAQ2

 

 

 

 

 