Telebahn AC Surge Protective Device 320V 275V 12.5kA 30kA 60kA SPD T1+T2 2P TUV 1 Phase Surge Suppressor
- Overview
- Inquiry
- Related Products

Technical data
Type |
BT P BCM12.5 275 RM/2P |
According to IEC 61643-11/EN 61643-11 |
Class I +Class II / Type 1 + Type 2 |
System mode |
1 Phase TN System (“ 2+0 " circuit) |
Nominal a.c. voltage [UN](50/60Hz) |
230V |
Rated voltage (max. continuous voltage) [Uc]( 50/60Hz ) |
320V |
Lightning impulse current (10/350μs) [Iimp] |
12.5kA |
Nominal discharge current (8/20μs) [In] |
30kA |
Max. discharge current (8/20μs) [Imax] |
60kA(Also passed 65kA) |
Voltage protection level at 320V [Up] |
≤ 1.8kV |
Voltage protection level at Iimp [Up] |
≤ 1.35kV |
Temporary overvoltage test value(UT ) |
355V/5sec |
Admissible short-current [Isccr] |
25kA |
Response time [tA] |
≤ 25ns |
Place of installation |
Indoor |
Max. back up fuse [F] |
160A gL/gG |
Degree of protection provided by the enclosure |
IP 20 |
Operating temperature range [Tu] |
-40°C...+80°C |
Specific energy(W/R) |
39.06kJ/ohms |
Cross-sectional area |
1.5mm2 ~ 25mm2 solid /35mm2 flexible |
Mounting on |
35mm DIN rail,According to EN 60715 |
Enclosure material |
Light Gray Thermoplastic, UL94-V0 |
Dimension |
2 mods (36mm wide) |
Test standards |
IEC 61643-11; EN 61643-11; GB/T 18802.11 |
Certification |
TUV; CE (LVD, EMC); CB; RoHS |
Type of remote signalling contact |
Switching contact |
Switching capacity |
AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A |
Cross-sectional area for remote signalling contact |
Max. 1.5mm2 solid / flexible |
Ordering information |
|
Type |
BT P BCM12.5 275 RM/2P |
Art.-No. |
801412 |
Packing unit |
1pc(s) |
Hightlight Features
• Pluggable module, for single-phase TN ( “2+0” circuit) system.
• High discharge capacity, quick response.
• Double thermal disconnector devices, providing more reliable protection.
• Green windows will change to red when fault and also provide remote alarm control at the same. time
• Surge protection device has passed TUV certification.
Summary
BT P BCM12.5 275 RM/2P(801412) power surge protector device is for installation at LPZ 0A-2 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I+II (Class B+C) for single-phase TN(“2+0” circuit) power supply system. Designed according to IEC 61643-11, EN 61643-11, GB/T 18802.11.