Technical data

Type

BT P BCM 25 RM/3P

Art.-No.

 800913

According to IEC 61643-11 / EN 61643-11

Class I + Class II    / Type 1 + Type 2 

Nominal AC voltage [UN]

230V/400V(50/60 Hz)

Rated voltage (max. continuous a.c. voltage) [ Uc ]

255V(50/60 Hz)

Total lightning impulse current (10/350μs) [Iimp] (L1+L2+L3+N-PE)

75kA

Lightning impulse current (10/350μs) [Iimp]

25kA

Nominal discharge current (8/20μs) [In]

50kA

Max. discharge current (8/20μs) [Imax]

75kA

Voltage protection level at In [Up]

≤ 1.5kV

Follow current extinguishing capability at Uc [ If ]

32A fuse will not be triggered at 2kArms

Response time [tA]  

≤ 100ns

TOV voltage  [ UT ]   

335V / 5sec

TOV 120min  [ UT ]

440V

Max. back up fuse (L) [F]

200A gL/gG(parallel wiring)

Max. back up fuse (L-L’) [F]

125A gL/gG(series wiring)

Operating temperature range [Tu]

-40°C...+80°C(parallel wiring)/-40°C...+60°C(series wiring)  

Thermal Protection

Yes

Max. cross-sectional area

35mmsolid / 50mm2 flexible

Mounting on

35mm DIN rail, EN 60715

Degree of protection

IP 20

Place of  installation

Indoor

Ports of Remote Terminal

1(or Optional)

Dimension

6mods (108mm)

Certification

CE (LVD, EMC); ROHS;REACH

Enclosure material

Light grey thermoplastic, UL94-V0

Operating state / Failure indication 

 Green / Red 

Test standards

IEC 61643-11:2011 ; EN 61643-11:2012; GB 18802.1-2011

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Warranty

3 Years

 

 6.jpg

 

Hightlight Features

1.  Three-phase lightning current surge arrester for TN-C system, Pluggable.

2. Adopt hermetical GDT technology, high follow current extinguishing capacity.

3. Extremely low voltage protection level.

4.  Double thermal disconnector devices, providing more reliable protection.

5. Green window will change to red when fault occurs, also provide remote alarm terminal  at the same.

6. Multifunctional connection for conductors and pure copper busbar.

7. Green window will change to red when fault occurs, also provide remote alarm terminal  at the same.

8. Recommended backup fuse / MCB 63A.

9. Suitable for use in three phase: 220V/380V(50/60 Hz), 240V/415V(50Hz), 230V/400V(50/60 Hz) AC systems.

10. Suitable for TN-C installations.

Mounting_BT P BCM 25 RM_3P.jpg

TN-C System

TN-C

Summary

3 Phase TNC Surge Protector BT P BCM 25 RM/3P(800913) is designed to protect low voltage devices from lightning and surge damages, Applied in modular Hybrid SPD Class I + Class II for 3 phase TN-C(“3+0” circuit) power supply system, mainly usedin power supply system such as power distribution-room,distribution-cabinet and other important power supply system.Designed according to IEC 61643-11:2011 ; EN 61643-11:2012; GB 18802.1-2011.