All Categories
AC SPD Class I

AC SPD Class I

Telebahn T1+T2 300V AC 12.5kA 30kA-60kA 3P+N Three-Phase Five-Wire Surge Protection SPD Surge Protector

Inquiry
  • Overview
  • Inquiry
  • Related Products

3

Product Description

 1.jpg

Technical data

Type

BT P BCM12.5 300/3+N

BT P BCM12.5 300 RM/3+N

Art.-No. 

801476

According to IEC 61643-11/EN 61643-11

 Class I + Class II  / Type 1+ Type 2

Type of remote signaling contact

-

Switching contact

Switching capacity(UN/IN)

-

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;75V/0.5A

Cross-sectional area for remote signaling contact

-

Max. 1.5mm2 (16AWG)solid/flexible

Number of remote terminals

0

1

AC Nominal voltage [UN]

230V/400V

Rated voltage (max. continuous voltage) [Uc]

300V(L-N)   255V(N-PE)

Power system frequency[Hz]

50/60 Hz

Lightning impulse current (10/350μs) [Iimp]

12.5kA(L-N)   50kA(N-PE)

Nominal discharge current (8/20μs) [In]

30kA(L-N)   50kA(N-PE)

Max. discharge current (8/20μs) [Imax]

60kA(L-N)   100kA(N-PE)

Voltage protection level at In [Up]

 ≤1.6kV(L-N)   ≤1.5kV(N-PE)

Short-circuit current rating[Isccr

25kA

TOV 120 min(safe fail)[UT]

520V(L-N)

TOV Withstand 200ms[UT]

1200V(N-PE)

Response time [tA]

≤ 25ns(L-N)  ≤ 100ns(N-PE)

Max. back up fuse [F]

160A gL/gG

Cross-sectional area 

25mm2(4AWG) solid / 35mm2(2AWG) flexible

Operating temperature range [Tu]

-40°C...+80°C

Mounting on 

35mm DIN rail, EN 60715 

Enclosure material

 Light gray thermoplastic, UL94-V0

Dimension 

4 mods (72mm wide) 

Test standards

 IEC 61643-11:2011 ; EN 61643-11:2012; GB/T 18802.11-2020

Certification

CE; RoHS

.png

Hightlight Features

1. Suitable for TT/TN-S(“3+1” circuit) installation,Pluggable module.

2. Use for Three-Phase Five-Wire system.

3. Consist of MOV and GDT thermal disconnection device.

4. High discharge capacity, quick response.

5. Multifunctional connection for conductors and busbar.

6. Double thermal disconnector devices, providing more reliable protection.

7. Green windows will change to red when fault and also provide remote alarm control at the same time.

8. Suitable for use in three phase: 220V/380V(50/60 Hz), 230V/400V(50/60 Hz) AC systems.

9. Crafted from selected flame-retardant enclosure, it effectively combats the spread of fire, buying critical time to protect life and property.

10. Powered by advanced European technology, it provides comprehensive and reliable protection for electrical equipment.

 

 

Summary

Telebahn Surge Protection BT P BCM12.5 300 RM/3+N(801476) is for installation at LPZ 0A-2 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I+II (Class B+C) for three-phase TT/TN-S ("3+1" circuit) power supply system. Designed according to Designed according to IEC 61643-11:2011 ; EN 61643-11:2012; GB /T 18802.11-2020.

1FAQ