All Categories
AC SPD Class II

AC SPD Class II

380V 385V 400V AC 20kA 40kA T2 3P KEMA Low Voltage 3 Phase Surge Protection SPD for Whole House

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description

 3

17.jpg

Technical data

Type

BT PCM TNC 275 RM

BT PCM TNC 385 RM

According to IEC 61643-11/EN 61643-11

Class II (class 2/C) / Type 2

System mode

3 Phase TN-C System (“ 3+0 " circuit)

Art.-No.

810829

810830

Nominal voltage  [UN](50/60Hz) 

230V/400V

230V/400V

Rated voltage (max. continuous voltage) [Uc] (50/60Hz)

275V

385V

Nominal discharge current (8/20μs) [In]

20kA

20kA

Max. discharge current (8/20μs) [Imax] 

40kA

40kA

Voltage protection level at In [Up]

≤ 1.3kV

≤ 1.8kV

Voltage protection level at 5kA [Up]

≤ 1.0kV

≤ 1.35kV

Response time [tA] 

≤ 25ns

Operating temperature range [Tu

-40°C...+80°C

 Operating state / Failure indication 

Green / Red 

Cross-sectional area

1.5mm2 ~ 25mm2 solid / 35mm2 flexible

Mounting on 

35mm DIN rail,  EN 60715

Enclosure material

Red(Purple/Gray,Optional) module / light gray base, thermoplastic, UL 94-V0

Degree of Protection 

IP 20

Number of remote terminals

1(or Optional)

Dimension 

3 mods (54mm wide) 

Certification

KEMA-KEUR; CB; CE; RoHS;REACH

Compliance

IEC 61643-11:2011 ; EN 61643-11:2012; GB 18802.1-2011

Type of remote signaling contact

Switching contact

Switching capacity a.c.

250V/0.5A

Switching capacity d.c.

250V/0.1A, 125V/0.2A, 75V/0.5A

Cross-sectional area for remote signaling contact

Max. 1.5mm2 solid/flexible

 

7.jpg

Hightlight Features

1.  Pluggable module, easy for installation and maintenance.

2. High discharge capacity, quick response.

3.  Double thermal disconnector devices, providing more reliable protection.

4.  Green window will change when fault and also provide remote alarm control at the same time.

5. Surge protection device has passed KEMA-KEUR certification.

6. Power system frequency:50/60 Hz.

7. Three phase 380V, 400V, 415V, 420V AC system compatible.

8. Recommended backup fuse / MCB 32A.

9. Suitable for TN-C installations.

19.jpg

Summary

BT PCM TNC 385 RM(810830) Power Surge Protector Device is for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class II (Class C) for 3 Phase TN-C("3+0" circuit) power supply system. Designed according to IEC 61643-11:2011 ; EN 61643-11:2012; GB 18802.1-2011.

Other

We have other three-phase AC voltage surge protectors available for you to choose from:

3 Phase 200V-415V AC Surge Protector and 3 Phase 208V-600V AC Surge Protector. 

 

Should you require further information, do not hesitate to reach out to us.

We're here to help – contact us anytime!

1FAQ

 

 

 

 

 

 

 

  

GET IN TOUCH