Telebahn 385V AC SPD 20kA-40kA 1P+N T2 AC House Surge Protector Low Voltage Surge Protection
- Overview
- Inquiry
- Related Products
Technical data
Type |
BT P C TT1+1 385 |
BT P C TT1+1 385 RM |
Art.-No. |
810111 |
|
According to IEC 61643-11/EN 61643-11 |
Class II (class 2/C) / Type 2 |
|
AC Nominal voltage[UN](50/60Hz) |
230V |
|
Rated voltage (max. continuous voltage) [Uc](50/60Hz) |
385V(L-N) 255V(N-PE) |
|
Nominal discharge current (8/20μs) [In] |
20kA(L-N) 40kA(N-PE) |
|
Max. discharge current (8/20μs) [Imax] |
40kA(L-N) 65kA(N-PE) |
|
Voltage protection level at In [Up] |
≤1.8kV(L-N) ≤1.5kV(N-PE) |
|
Voltage protection level at 5kA [Up] |
≤1.35kV(L-N) |
|
Response time [tA] |
≤ 25ns(L-N) ≤ 100ns(N-PE) |
|
TOV withstand 5sec[UT] |
335V(L-N) |
|
TOV 120 min(safe fail)[UT] |
440V(L-N) |
|
TOV withstand 200ms[UT] |
1200V(N-PE) |
|
Follow current extinguishing |
100Arms(N-PE) |
|
Max. back up fuse [F] |
125A gL/gG |
|
Short circuit withstand capability |
25kArms |
|
Cross-sectional area |
1.5mm2 ~ 25mm2 solid / 35mm2 flexible |
|
Operating temperature range [Tu] |
-40°C...+80°C |
|
Mounting on |
35mm DIN rail, EN 60715 |
|
Enclosure material |
Purple thermoplastic, UL94-V0 |
|
Dimension |
2 mods (36mm wide) |
|
Compliance |
IEC 61643-11:2011 ; EN 61643-11:2012; GB/T 18802.11-2020 |
|
Certification |
CE; RoHS |
|
Number of remote terminals |
0 |
1 |
Type of remote signaling contact |
- |
Switching contact |
Switching capacity(UN/IN) |
- |
AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;75V/0.5A |
Cross-sectional area for remote signaling contact |
- |
Max. 1.5mm2 (16AWG)solid/flexible |
Hightlight Features
1. Pluggable module, AC SPD 1P+N 385V 20-40kA T2, easy for installation and maintenance.
2. Consist of High Energy MOV + High Energy GDT and thermal disconnection devices.
3. High discharge capacity, quick response.
4. Double thermal disconnector devices, providing more reliable protection.
5. Green window will change to red when fault occurs and also provide remote alarm control at the same time.
6. Suitable for use in single phase 220V-240V AC systems.
7. Suitable for TT/ TN installations.
Summary
BT P C TT1+1 385 RM Designed for installation in LPZ 0B-1 or higher zones, this surge protection device safeguards low-voltage equipment from power surges and remote terminal is optional.
Application:Pluggable SPD Class II for single-phase TT/TN (“1+1” circuit) power supply systems.
Compliance Standards:IEC 61643-11:2011;EN 61643-11:2012;GB/T 18802.11-2020.