All Categories
AC SPD Class II

AC SPD Class II

SPD Surge Protector 275V 255V 10kA 20kA T2+T3 3 Phase Lightning Protector SPD

Inquiry
  • Overview
  • Inquiry
  • Related Products
Product Description
3
 13.jpg

Technical Data

Type  

 

BT PCM20 150 RM/3+N

 

 

BT PCM20 275 RM/3+N

 

 

BT PCM20 320 RM/3+N

 

BT PCM20 440 RM/3+N

Art.-No.

810856 810857 810 884 810859

Nominal a.c. voltage[UN](50/60Hz) 

 120V/240V  230V/400V   230V/400V  400V/690V 

Rated voltage (max. continuous voltage) [Uc] (L-N / N-PE(50/60Hz) 

150V/255V

275V/255V

320V/255V

440V/255V

Nominal discharge current (8/20μs) [In] (L-N / N-PE)

10kA /20kA

10kA /20kA

10kA /20kA

10kA /20kA

Max. discharge current (8/20μs) [Imax] (L-N / N-PE)

20kA /40kA

20kA /40kA

20kA /40kA

20kA /40kA

Voltage protection level at In [Up](L-N / N-PE)

≤ 0.7kV/ ≤ 1.5kV

≤ 1.0kV/≤ 1.5kV

≤ 1.2kV/ ≤ 1.5kV

≤ 1.8kV/≤ 1.5kV

TOV voltage(L-N)

 180V/5sec  335V/5sec  335V/5sec  580V/5sec

TOV 120min(L-N)

230V 440V 440V 765V

According to IEC 61643-11 / EN 61643-11

Class II + Class III / Type 2 + Type 3

Open circuit voltage (1.2/50μs)

20kV

TOV voltage[N-PE]

1200V/200ms

Operating temperature range [Tu]

-40°C...+80°C

Cross-sectional area

1.5mm2 ~ 25mm2 solid / 35mm2 flexible

Response time [tA](L-N / N-PE)

≤ 25ns / ≤ 100ns

Degree of protection

IP 20 

Number of remote terminals

1 (or Optional)

Max. back up fuse [F]

125A gL/gG

Place of installation

Indoor

Mounting on

35mm DIN rail,  EN 60715 

Enclosure material

Purple (module) & light grey (base) thermoplastic, UL94-V0

Dimension

4 mods(72mm wide)

Test standards

IEC 61643-11:2011 ; EN 61643-11:2012; GB 18802.1-2011

Certification

 CE(LVD,EMC);RoHS;REACH

Type of remote signalling contact

Switching contact

Switching capacity

AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A

Cross-sectional area for remote signalling contact

Max. 1.5mm2 solid / flexible

Warranty

3 Years

17.jpg
 

Hightlight Features

1. Pluggable module, easy for installation and maintenance.

2. Combined class ll 3 phase surge arresters for TT/TN-S system( “3+1” circuit).

3. Consist of High Energy MOV + High Energy GDT and thermal disconnection devices.

4.  High discharge capacity, quick response.

5. Double thermal disconnector devices, providing more reliable protection.

6. Green window will change to red when fault occurs and also provide remote alarm control at the same time.

7. Prewired unit, integrated base design.

27.jpg

TT System

TT

Summary

AC Surge Protector BT PCM20 275 RM/3+N(810857) is for installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge damage. Applied in pulggable SPD Class II +Class III (Class C+Class D) for TT/TN-S(“3+1” circuit) power supply system. Designed according to IEC 61643-11:2011 ; EN 61643-11:2012; GB 18802.1-2011.

 

1FAQ

GET IN TOUCH